| HENKEL | Alpla | Vetromeccanica | AUTEFA | |
|
||
|
| ---------------------- | ------------------------------------------------------------------------------------------------------------ | ---------------------------------------------------------------------------------------------------- | ---------------------------------------------------------------- | ---------------------------------------------------------------------------------------- |
|
||
|
| Before Changeover | Sends IDH_BTL_NEXT number to be validated | | | |
|
||
|
| _Data_To_EbConvey[38]_ | | | | |
|
||
|
| | Validates IDH_BTL_NEXT is valid number and send acknowledge | | | |
|
||
|
| | _Data_From_EbConvey[0].2_ | | | |
|
||
|
| Step 1 | Operator manually selects "Line Clearance" (?) and send signal "0" on "CalculatedBottlesRemainingToFill". | | | |
|
||
|
| | _Data_To_EbConvey[23]_ | | | |
|
||
|
| Step 2 | | Stops taking bottles out of trays and sends what is already on the tables and conveyors. | Emptying Merger and Line | Stops taking bottles out of trays and sends what is already on the tables and conveyors. |
|
||
|
| | | _N/A_ | _TG10 Send 0 in Bottles for Actual Batch_ | |
|
||
|
| Step 3 | Operator verifies line is empty and sends "changeover request" signal after last bottle goes thorugh filler. | | | |
|
||
|
| | _Data_To_EbConvey[0].0_ | | | |
|
||
|
| Step 4 | | Operator verifies line is empty and sends "line is busy with changeover", confirming on Popup screen | | |
|
||
|
| | | _Data_From_EbConvey[0].0_ | | |
|
||
|
| Step 5 | | | Starts changeover | Starts changeover |
|
||
|
| | | | _Data_From_EbConvey[0].0_ | _Data_From_EbConvey[0].0_ |
|
||
|
| Step 6 | | | Ends changeover. Sends signal "Changeover is finished and ready. | Ends changeover. Sends signal "Changeover is finished and ready. |
|
||
|
| | | | _Data_From_EbConvey[0].1_ | _Data_From_EbConvey[0].1_ |
|
||
|
| | | | | |
|
||
|
| | | | | |
|
||
|
| Step 7 | Send Reset counters signal | | Reset Counters | |
|
||
|
| | _Data_To_EbConvey[0].1_ | | | |
|
||
|
| Step 8 | Send new value on "CalculatedBottlesRemainingToFill". | | | |
|
||
|
| | _Data_To_EbConvey[23]_ | | | |
|
||
|
| Step 9 | Send Changeover Complete. To be considered "Production Ready" | Starts conveying bottles. | Finish Chanover Cycle | |
|
||
|
| | _Data_To_EbConvey[0].2_ | | | |
|
||
|
|
||
|
|
||
|
|
||
|
# Batch Lifecycle Process Documentation
|
||
|
|
||
|
## Overview
|
||
|
|
||
|
This document details the step-by-step process of a batch changeover in the production line, including all interactions between HENKEL, ALPLA, Vetromeccanica, and AUTEFA systems.
|
||
|
|
||
|
## System Roles
|
||
|
|
||
|
- **HENKEL**: Controls filling process and initiates batch changes
|
||
|
- **ALPLA**: Manages bottle production and validates batch data
|
||
|
- **Vetromeccanica**: Coordinates conveyor systems and inter-system communications
|
||
|
- **AUTEFA**: Handles empty bottle logistics and tray loading
|
||
|
|
||
|
## Pre-Changeover Phase
|
||
|
|
||
|
### Batch Validation
|
||
|
1. **HENKEL → ALPLA**
|
||
|
- Sends next batch bottle ID (IDH_BTL_NEXT)
|
||
|
- Location: `Data_To_EbConvey[38]`
|
||
|
|
||
|
2. **ALPLA Response**
|
||
|
- Validates IDH_BTL_NEXT number
|
||
|
- Sends acknowledgment
|
||
|
- Signal: `Data_From_EbConvey[0].2`
|
||
|
|
||
|
## Changeover Process
|
||
|
|
||
|
### Step 1: Line Clearance Initiation
|
||
|
- **HENKEL Action**:
|
||
|
- Operator selects "Line Clearance"
|
||
|
- Sets "CalculatedBottlesRemainingToFill" to 0
|
||
|
- Location: `Data_To_EbConvey[23]`
|
||
|
|
||
|
### Step 2: Production Stop
|
||
|
- **Vetromeccanica Actions**:
|
||
|
- Stops bottle unloading from trays
|
||
|
- Continues processing bottles already on conveyors
|
||
|
- **AUTEFA Actions**:
|
||
|
- Initiates merger and line emptying
|
||
|
- Updates TG10 telegram with 0 in Bottles for Actual Batch
|
||
|
|
||
|
### Step 3: Line Verification
|
||
|
- **HENKEL Action**:
|
||
|
- Operator verifies empty line
|
||
|
- Sends changeover request after last bottle passes filler
|
||
|
- Signal: `Data_To_EbConvey[0].0`
|
||
|
|
||
|
### Step 4: Changeover Confirmation
|
||
|
- **Vetromeccanica Action**:
|
||
|
- Operator verifies empty line
|
||
|
- Confirms "line busy with changeover" via popup
|
||
|
- Signal: `Data_From_EbConvey[0].0`
|
||
|
|
||
|
### Step 5: Changeover Execution
|
||
|
- **AUTEFA & Vetromeccanica**:
|
||
|
- Start changeover process
|
||
|
- Signal: `Data_From_EbConvey[0].0`
|
||
|
|
||
|
### Step 6: Completion Confirmation
|
||
|
- **AUTEFA & Vetromeccanica**:
|
||
|
- Send "Changeover finished and ready" signal
|
||
|
- Signal: `Data_From_EbConvey[0].1`
|
||
|
|
||
|
## Post-Changeover Phase
|
||
|
|
||
|
### Step 7: Counter Reset
|
||
|
- **HENKEL Action**:
|
||
|
- Sends reset counters signal
|
||
|
- Signal: `Data_To_EbConvey[0].1`
|
||
|
- **AUTEFA Action**:
|
||
|
- Resets internal counters
|
||
|
|
||
|
### Step 8: Production Parameters
|
||
|
- **HENKEL Action**:
|
||
|
- Updates "CalculatedBottlesRemainingToFill" with new value
|
||
|
- Location: `Data_To_EbConvey[23]`
|
||
|
|
||
|
### Step 9: Production Resume
|
||
|
- **HENKEL Action**:
|
||
|
- Sends "Changeover Complete" signal
|
||
|
- Signal: `Data_To_EbConvey[0].2`
|
||
|
- **Vetromeccanica Action**:
|
||
|
- Starts conveying bottles
|
||
|
- **AUTEFA Action**:
|
||
|
- Completes changeover cycle
|
||
|
|
||
|
## Communication Flow Diagram
|
||
|
|
||
|
```mermaid
|
||
|
sequenceDiagram
|
||
|
participant H as HENKEL
|
||
|
participant A as ALPLA
|
||
|
participant V as Vetromeccanica
|
||
|
participant AU as AUTEFA
|
||
|
|
||
|
H->>A: Send IDH_BTL_NEXT
|
||
|
A->>H: Validate & Acknowledge
|
||
|
H->>V: Set CalculatedBottlesRemainingToFill = 0
|
||
|
V->>AU: Stop Unloading
|
||
|
H->>V: Send Changeover Request
|
||
|
V->>V: Confirm Empty Line
|
||
|
V->>AU: Start Changeover
|
||
|
AU->>V: Confirm Changeover Complete
|
||
|
H->>V: Reset Counters
|
||
|
H->>V: New Bottle Count
|
||
|
H->>V: Production Ready
|
||
|
```
|
||
|
|
||
|
## Signal Reference Table
|
||
|
|
||
|
| Step | Signal | Location | Description |
|
||
|
|------|---------|-----------|-------------|
|
||
|
| Pre-Change | IDH_BTL_NEXT | Data_To_EbConvey[38] | Next batch bottle ID |
|
||
|
| Validation | Acknowledge | Data_From_EbConvey[0].2 | Batch validation |
|
||
|
| Initiation | Zero Count | Data_To_EbConvey[23] | Remaining bottles count |
|
||
|
| Request | Changeover | Data_To_EbConvey[0].0 | Start changeover |
|
||
|
| Confirmation | Line Busy | Data_From_EbConvey[0].0 | Line status |
|
||
|
| Completion | Ready | Data_From_EbConvey[0].1 | Line ready |
|
||
|
| Reset | Counters | Data_To_EbConvey[0].1 | Reset counters |
|
||
|
| Resume | Complete | Data_To_EbConvey[0].2 | Production ready |
|
||
|
|
||
|
## Error Handling
|
||
|
|
||
|
### Validation Errors
|
||
|
- Invalid batch number detection
|
||
|
- Communication timeout handling
|
||
|
- Line status verification failures
|
||
|
|
||
|
### Process Safeguards
|
||
|
- Multiple operator confirmations required
|
||
|
- Line emptiness verification
|
||
|
- Status signal validation
|
||
|
|
||
|
### Recovery Procedures
|
||
|
1. Counter synchronization check
|
||
|
2. Line status verification
|
||
|
3. Communication reset if needed
|
||
|
4. Manual intervention protocols
|
||
|
|
||
|
|
||
|
***
|
||
|
|
||
|
# Vetromeccanica Software Implementation Guide
|
||
|
|
||
|
## Software Architecture
|
||
|
|
||
|
### PLC Distribution
|
||
|
1. **Q1 PLCs (Client Side)**
|
||
|
- Main communication interface with Henkel
|
||
|
- Manages line controllers Q2-Q4
|
||
|
- Handles real-time batch data processing
|
||
|
|
||
|
2. **Supervisor PLC (Server Side)**
|
||
|
- Central communication hub
|
||
|
- Manages AUTEFA telegrams
|
||
|
- Provides ALPLA OPC-UA interface
|
||
|
- Handles SKU database and searches
|
||
|
|
||
|
## Data Structures
|
||
|
|
||
|
### Client Side Structures
|
||
|
|
||
|
```pascal
|
||
|
// FromHenkel Communication Structure
|
||
|
TYPE "FromHenkelv2_U"
|
||
|
STRUCT
|
||
|
di : Array[0..49] of DINT; // Raw data from Henkel
|
||
|
STW : "Bool32_U"; // Status word bits
|
||
|
LineStatus : Struct
|
||
|
di0 : "Bool32_U"; // Line status bits
|
||
|
END_STRUCT;
|
||
|
SignalExchange : Struct // Line signals
|
||
|
Filler : Struct
|
||
|
CalculatedBottlesRemainingToFill : DINT;
|
||
|
END_STRUCT;
|
||
|
END_STRUCT;
|
||
|
AB_IDH_BTL : Array[0..11] of CHAR; // Current batch ID
|
||
|
NB_IDH_BTL : Array[0..11] of CHAR; // Next batch ID
|
||
|
PO_NUMBER : Array[0..11] of CHAR; // Current order
|
||
|
PO_NUMBER_NEXT : Array[0..11] of CHAR; // Next order
|
||
|
ABBottlesNumber : DINT; // Current batch count
|
||
|
NBBottlesNumber : DINT; // Next batch count
|
||
|
END_STRUCT;
|
||
|
END_TYPE
|
||
|
```
|
||
|
|
||
|
### Server Side Structures
|
||
|
|
||
|
```pascal
|
||
|
// SKU Information Structure
|
||
|
TYPE "StSku_U"
|
||
|
STRUCT
|
||
|
Av : DInt; // Article Variant ID
|
||
|
AvDesc : String[36]; // Description
|
||
|
ProdFamily : DInt; // Product Family
|
||
|
CustomArticleNum : String[12]; // Customer Article Number
|
||
|
END_STRUCT;
|
||
|
END_TYPE
|
||
|
|
||
|
// AUTEFA Message Header
|
||
|
TYPE "AUTEFA_message_header"
|
||
|
STRUCT
|
||
|
message_length : Int;
|
||
|
endian_format : Word := 16#4321;
|
||
|
telegram_number : Int;
|
||
|
task : Int := 1;
|
||
|
error_number : DInt;
|
||
|
send_client_ID : "Client_ID";
|
||
|
timestamp : "TX_Time";
|
||
|
END_STRUCT;
|
||
|
END_TYPE
|
||
|
```
|
||
|
|
||
|
## Key Functions Implementation
|
||
|
|
||
|
### 1. Byte Processing (Q1)
|
||
|
|
||
|
```pascal
|
||
|
// Process incoming Henkel data
|
||
|
FOR #i := 0 TO 49 DO
|
||
|
#atFromHenkel[#i] := "FromHenkel".di[#i];
|
||
|
CASE #i OF
|
||
|
0, 10, 20, 35..40, 44..49: // Control words and IDs
|
||
|
#diAppo.%B3 := #atFromHenkel[#i].%B2;
|
||
|
#diAppo.%B2 := #atFromHenkel[#i].%B3;
|
||
|
#diAppo.%B1 := #atFromHenkel[#i].%B0;
|
||
|
#diAppo.%B0 := #atFromHenkel[#i].%B1;
|
||
|
ELSE // Process data
|
||
|
#diAppo.%W0 := #atFromHenkel[#i].%W1;
|
||
|
#diAppo.%W1 := #atFromHenkel[#i].%W0;
|
||
|
END_CASE;
|
||
|
#atFromHenkel[#i] := #diAppo;
|
||
|
END_FOR;
|
||
|
```
|
||
|
|
||
|
### 2. SKU Search (Supervisor)
|
||
|
|
||
|
```pascal
|
||
|
// Search SKU in ALPLA database
|
||
|
IF NOT "LineN[#i].SearchEnd" THEN
|
||
|
IF "LineN[#i].i" >= 249 THEN
|
||
|
"LineN[#i].SkuActualNotFound" := TRUE;
|
||
|
"LineN[#i].SkuActualReq.Av" := 0;
|
||
|
"LineN[#i].SkuActualReq.ProdFamily" := 0;
|
||
|
"LineN[#i].SearchActualSku" := FALSE;
|
||
|
ELSIF "LineN[#i].ReqActualCustomProdNum" =
|
||
|
"AlplaSkuList[LineN[#i].i].CustomArticleNum" THEN
|
||
|
"LineN[#i].SkuActualReq" := "AlplaSkuList[LineN[#i].i]";
|
||
|
"LineN[#i].SearchActualSku" := FALSE;
|
||
|
ELSE
|
||
|
"LineN[#i].i" += 1;
|
||
|
END_IF;
|
||
|
END_IF;
|
||
|
```
|
||
|
|
||
|
### 3. AUTEFA Telegram Preparation (Supervisor)
|
||
|
|
||
|
```pascal
|
||
|
// Prepare TG10 Production Info
|
||
|
"TG10_send.DATA.Filling_Line" := #LineNumber;
|
||
|
|
||
|
// Actual batch data
|
||
|
Strg_TO_Chars(
|
||
|
Strg := "BatchActual.BatchNumber",
|
||
|
pChars := 0,
|
||
|
Cnt => #uiCnt,
|
||
|
Chars := "TG10_send.DATA.Batch_ID"
|
||
|
);
|
||
|
|
||
|
"TG10_send.DATA.Active_Batch_Target_1000" :=
|
||
|
DINT_TO_INT("ToAutefa.TG10_ProductionInfo" / 1000);
|
||
|
|
||
|
"TG10_send.DATA.Active_Batch_Target_Units" :=
|
||
|
DINT_TO_INT("ToAutefa.TG10_ProductionInfo" MOD 1000);
|
||
|
|
||
|
"TG10_send.DATA.Active_Batch_Article_Variant_ID" :=
|
||
|
"WriteData_D.ToQ1.FromAlpla.ActualSku.Av";
|
||
|
```
|
||
|
|
||
|
## Data Flow Processing
|
||
|
|
||
|
### 1. Q1 Processing Sequence
|
||
|
|
||
|
```mermaid
|
||
|
graph TD
|
||
|
A[Receive Henkel Data] --> B[Byte Swap Processing]
|
||
|
B --> C[Update Local Variables]
|
||
|
C --> D[Send to Line PLCs]
|
||
|
C --> E[Send to Supervisor]
|
||
|
```
|
||
|
|
||
|
### 2. Supervisor Processing Sequence
|
||
|
|
||
|
```mermaid
|
||
|
graph TD
|
||
|
A[Receive Q1 Data] --> B[SKU Search]
|
||
|
B --> C[Format Data]
|
||
|
C --> D[Prepare AUTEFA Telegram]
|
||
|
C --> E[Update OPC-UA Data]
|
||
|
```
|
||
|
|
||
|
## Error Handling Implementation
|
||
|
|
||
|
### 1. Communication Monitoring
|
||
|
|
||
|
```pascal
|
||
|
// Monitor Q1-Henkel communication
|
||
|
"T_LostComHenkel".TON(
|
||
|
IN := NOT "TR_LostComHenkel".Q AND
|
||
|
NOT "ToSV.STW.QE1.LostComQ1",
|
||
|
PT := T#60s
|
||
|
);
|
||
|
"ToSV.STW.QE1.LostComHenkel" := "T_LostComHenkel".Q;
|
||
|
```
|
||
|
|
||
|
### 2. SKU Validation
|
||
|
|
||
|
```pascal
|
||
|
// Validate SKU data
|
||
|
IF "LineN[#i].SearchActualSku" AND "LineN[#i].i" >= 249 THEN
|
||
|
// SKU not found handling
|
||
|
"LineN[#i].SkuActualNotFound" := TRUE;
|
||
|
"LineN[#i].SkuActualReq.Av" := 0;
|
||
|
"LineN[#i].SkuActualReq.ProdFamily" := 0;
|
||
|
"LineN[#i].SkuActualReq.CustomArticleNum" := '';
|
||
|
"LineN[#i].SkuActualReq.AvDesc" := '';
|
||
|
END_IF;
|
||
|
```
|
||
|
|
||
|
## Line Index Configuration
|
||
|
|
||
|
Each line's data is managed through a consistent index system:
|
||
|
|
||
|
```pascal
|
||
|
CASE LineIndex OF
|
||
|
0: // Fill_TL21_L23
|
||
|
#locChar := "TL21_ReadData_D".FromQ1.FromHenkel.AB_IDH_BTL;
|
||
|
1: // Fill_TL22_L25
|
||
|
#locChar := "TL22_ReadData_D".FromQ1.FromHenkel.AB_IDH_BTL;
|
||
|
2: // Fill_TL23_L43
|
||
|
#locChar := "TL23_ReadData_D".FromQ1.FromHenkel.AB_IDH_BTL;
|
||
|
3: // Fill_TL25_L41
|
||
|
#locChar := "TL25_ReadData_D".FromQ1.FromHenkel.AB_IDH_BTL;
|
||
|
4: // Fill_TL26_L42
|
||
|
#locChar := "TL26_ReadData_D".FromQ1.FromHenkel.AB_IDH_BTL;
|
||
|
5: // Fill_TL27_L40
|
||
|
#locChar := "TL27_ReadData_D".FromQ1.FromHenkel.AB_IDH_BTL;
|
||
|
END_CASE;
|
||
|
```
|
||
|
|
||
|
## Important Memory Mappings
|
||
|
|
||
|
### Henkel Data Array Map
|
||
|
```
|
||
|
di[0-49] Layout:
|
||
|
- Current Batch Data:
|
||
|
- PO_NUMBER: di[44-46]
|
||
|
- IDH_BTL: di[35-37]
|
||
|
- Next Batch Data:
|
||
|
- PO_NUMBER: di[47-49]
|
||
|
- IDH_BTL: di[38-40]
|
||
|
- Next+1 Batch Data:
|
||
|
- PO_NUMBER: di[1-3]
|
||
|
- IDH_BTL: di[7-9]
|
||
|
- IDH_CON: di[4-6]
|
||
|
```
|
||
|
|
||
|
### Critical Status Bits
|
||
|
```
|
||
|
STW Bits:
|
||
|
- [0]: Changeover Request
|
||
|
- [1]: Counter Reset
|
||
|
- [2]: Production Ready
|
||
|
- [31]: Life Bit
|
||
|
|
||
|
Line Status:
|
||
|
- [0]: Line Empty
|
||
|
- [1]: Changeover Active
|
||
|
- [2]: Line Ready
|
||
|
```
|
||
|
|
||
|
## Debug Tips
|
||
|
|
||
|
1. **Communication Issues**
|
||
|
- Check life bit timing (bit 31)
|
||
|
- Verify byte swap patterns
|
||
|
- Monitor communication counters
|
||
|
|
||
|
2. **SKU Search Problems**
|
||
|
- Enable search debugging flags
|
||
|
- Log CustomArticleNum comparisons
|
||
|
- Verify AlplaSkuList content
|
||
|
|
||
|
3. **Telegram Failures**
|
||
|
- Validate header structure
|
||
|
- Check message length calculations
|
||
|
- Monitor acknowledgment timing
|
||
|
|
||
|
## Common Implementation Pitfalls
|
||
|
|
||
|
4. **Byte Ordering**
|
||
|
- Always use correct swap pattern based on data type
|
||
|
- Verify endianness in telegram headers
|
||
|
- Test with known data patterns
|
||
|
|
||
|
5. **String Handling**
|
||
|
- Zero-pad incomplete strings
|
||
|
- Handle empty/null characters
|
||
|
- Verify string length limits
|
||
|
|
||
|
6. **Counter Management**
|
||
|
- Synchronize counters after resets
|
||
|
- Handle rollover conditions
|
||
|
- Validate counter arithmetic
|