{"path":"01-Documentation/Inverters/Lenze/adjuntos/Pasted image 20241021163812.png","text":"Parameter [ raa /seting e/ it seing fi ] 0x4008:001 | Process input data: AC Drive control word Mappable control word with bit assignment in compliance with (P592.01) (Process data IN: AC control word) EtherNet/IP™ AC drive profile. 0x0000 ... [0x0000] ... OXFFFF Run forward (CW) Bits are only evaluated if bit 5 = \"1\". Run reverse (CCW) For the exact logic, see the above truth table. Bit 5| Activate network control If bit 5 = \"1\" and 0x2631:037 (P400.37) = \"Network control active [114]\": Allbits of the AC Drive control word are evaluated. Ifbit 5 = \"0\" or 0x2631:037 (P400.37) = \"Not connected [0]\": * Bit0,1,6,12, 13,14, 15 of the AC drive control word are not evaluated (ignored). * Active control source is the \"Flexible 1/O configuration”. } Changing the control source during operation C83 Bit 6| Activate network setpoint 0 = the standard setpoint source selected in 0x2860:001 (P201.01) is used. 1= network setpoint is used. Bit 6 is only evaluated if bit 5 = \"1\". For control without bit 5, the \"Network setpoint active [116]\" selection must be set in 0x2631:017 (P400.17). Disable inverter Bits are only evaluated if bit 5 = \"1\". Activate quick stop Bit_14 | Disable PID controlling Activate DC braking","libVersion":"0.3.2","langs":"eng+ita"}