### Layout:
|
||
|
***
|
||
|
![[Pasted image 20240408155616.png]]
|
||
|
|
||
|
#### Added photocells:
|
||
|
***
|
||
|
![[Pasted image 20240408151720.png|425]]
|
||
|
|
||
|
|
||
|
### The flow now is:
|
||
|
***
|
||
|
|
||
|
1. Neumatic Divider M90:
|
||
|
1. Left: go to M90 - M91 - M92 - M98 - M99
|
||
|
1. Dosser: M161 (minimotor Guide) - M157/M158 ( sinamics G120 one inverter two motors )
|
||
|
2. Elevator: M93 - M94/M122
|
||
|
3. Pneumatic Ejector
|
||
|
4. M100 - M101
|
||
|
5. ==Labeler==
|
||
|
6. M102
|
||
|
7. Combiner M103 : S1-M103
|
||
|
8. ~~M107~~ : infeed Filler
|
||
|
9. ==Filler==
|
||
|
2. Right:
|
||
|
1. M95 - M96 - M97
|
||
|
2. ~~M104 - M105~~
|
||
|
3. Combiner M106 : S1-M106
|
||
|
4. ~~M107~~ : infeed Filler
|
||
|
5. ==Filler==
|
||
|
|
||
|
### Synoptic changes:
|
||
|
***
|
||
|
|
||
|
![[Pasted image 20240311170450.png]]
|
||
|
|
||
|
* Added Zone 7 and updated Zone 4,5 and 6.
|
||
|
|
||
|
|
||
|
#### Used Logic "FC TTOP AUTEFA 2 PH"
|
||
|
***
|
||
|
* This logic uses 4 fix speed
|
||
|
* 3 Sensors:
|
||
|
* NxSA : Next motor SA photocell -> Timer 04 / 05-06 Jam
|
||
|
* NxSB: Next motor SB photocell -> Timer 06 Jam
|
||
|
* SA : actual motor SA photocell -> Timer 03 / 05 Jam
|
||
|
* SA : Timer 01: SA
|
||
|
* SB : Timer 02: SB
|
||
|
|
||
|
* FIX1: ( empty )
|
||
|
* By default
|
||
|
* FIX2: only 1 photocell accumulation
|
||
|
* NxSA e non SA e SB
|
||
|
* FIX3: 2 photocells accumulation
|
||
|
* No SA + SB + NxSA o SA + SB NO NxSA : Two photocells but not 3
|
||
|
* FIX4: 3 photocells ( Full )
|
||
|
* All 3 photocells
|
||
|
|
||
|
|
||
|
#### Doser M157/M158 with thermal sensor
|
||
|
***
|
||
|
* Added sensor signals on E47.5 / E47.6
|
||
|
* Added Allarm "DB Warnings".W173_01_7
|
||
|
|
||
|
### Added Minimotor logic for Guide changer
|
||
|
***
|
||
|
|
||
|
* Added Minimotor Logic FC1155 for the M161 on the PLC
|
||
|
* Called from FC380
|
||
|
* Added 595 page on both HMI to setup the formats and allow manuals.
|
||
|
|
||
|
|
||
|
![[Pasted image 20240311121916.png]]
|
||
|
|
||
|
* Diametro Bottiglia and Tolleranza Diametro are ==saved on the Recipe== as an array.
|
||
|
* Add popup for homing
|
||
|
*
|
||
|
![[Pasted image 20240403112756.png]]
|
||
|
|
||
|
* On this popup the user must put the length that is currently between the rubber conveyors.
|
||
|
|
||
|
![[Pasted image 20240403113511.png|425]]
|
||
|
#### Added Motors to FC371:
|
||
|
|
||
|
```pascal
|
||
|
L %DB319.DBB291 // Motor M98
|
||
|
T %DB371.DBB49
|
||
|
|
||
|
L %DB320.DBB291 // Motor M99
|
||
|
T %DB371.DBB50
|
||
|
|
||
|
L %DB321.DBB291 // Motor M100
|
||
|
T %DB371.DBB51
|
||
|
|
||
|
L %DB322.DBB291 // Motor M101
|
||
|
T %DB371.DBB52
|
||
|
|
||
|
L %DB323.DBB291 // Motor M102
|
||
|
T %DB371.DBB53
|
||
|
|
||
|
L %DB324.DBB291 // Motor M103
|
||
|
T %DB371.DBB54
|
||
|
|
||
|
L %DB325.DBB291 // Motor M157/158
|
||
|
T %DB371.DBB55
|
||
|
```
|
||
|
|
||
|
#### Added logic for Q1 on FC372
|
||
|
***
|
||
|
![[Pasted image 20240312154910.png]]
|
||
|
|
||
|
|
||
|
|
||
|
### Added signals from and to Henkel
|
||
|
***
|
||
|
##### TO HENKEL:
|
||
|
***
|
||
|
![[Pasted image 20240313122842.png]]
|
||
|
DB34:
|
||
|
![[Pasted image 20240313122638.png]]
|
||
|
|
||
|
##### FROM HENKEL:
|
||
|
***
|
||
|
![[Pasted image 20240313122858.png]]
|
||
|
DB33:
|
||
|
![[Pasted image 20240313122722.png]]![[Pasted image 20240313122746.png]]
|
||
|
|
||
|
#### Added new Group of EMD for the Q5 line
|
||
|
***
|
||
|
* DB224
|
||
|
|
||
|
![[Pasted image 20240321151155.png|475]]
|
||
|
|
||
|
|
||
|
#### Flow selection Check:
|
||
|
***
|
||
|
|
||
|
![[Pasted image 20240408123359.png]]
|
||
|
|
||
|
This page helps the operator to ensure all flows are ok.
|
||
|
|
||
|
##### Added Alarms:
|
||
|
* 173/02/0 General - GUIDE M103 NOT OK FOR THE FLOW SELECTED
|
||
|
* 173/02/1 General - DIVIDER M90 NOT OK FOR THE FLOW SELECTED
|
||
|
* 173/02/2 General - DIVIDER LINE FLOW NOT OK FOR THE FLOW SELECTED
|
||
|
* 173/02/3 General - HENKEL SUPERVISION FLOW NOT CORRECT
|
||
|
|
||
|
|
||
|
#### Selectors Page:
|
||
|
***
|
||
|
|
||
|
![[Pasted image 20240408123502.png]]
|
||
|
|
||
|
##### Pause lowerator infeed:
|
||
|
- With this selector the lowerator can be emptied to prevent damaging the bottles
|
||
|
|
||
|
##### Added Alarm:
|
||
|
* `"DB Warnings".W173_06_1` : 173/06/1 General - Stop bottle flow on lowerator
|
||
|
|
||
|
##### Flow:
|
||
|
- On this page can be selected the Flow requested. Based on this selection the selected flow motor will be enabled and the other will be disabled.
|
||
|
|
||
|
|
||
|
#### PE Labeler Counting
|
||
|
***
|
||
|
|
||
|
* Added 3 photocells:
|
||
|
* Reset signal from Henkel from Q1
|
||
|
* "FromQ1_D".FromHenkel.SignalExchange.Labeller.di14[2]
|
||
|
* This signal must be connected with "FromQ1_D".FromHenkel.STW."di0.x"[1] from Q3
|
||
|
* On Q1 with "ToQ3_D".FromHenkel.STW."di0.x"[1]
|
||
|
* On FC9 segm 10
|
||
|
|
||
|
|
||
|
##### On Q4:
|
||
|
***
|
||
|
|
||
|
| | Q4->Q1 | Q1->Q4 |
|
||
|
| ----- | ------------------------------------------- | ----------------------------------------------------- |
|
||
|
| Count | "ToQ1_D".ToHenkel.Counter.DischargeLabeller | |
|
||
|
| Reset | | "FromQ1_D".FromHenkel.SignalExchange.Labeller.di14[2] |
|
||
|
|
||
|
##### On Q1 PLC:
|
||
|
***
|
||
|
FC32 - Net 10:
|
||
|
```pascal
|
||
|
// Labeller counter Reset
|
||
|
"ToQ4_D".FromHenkel.SignalExchange.Labeller.di14[2] := "ToQ3_D".FromHenkel.STW."di0.x"[1];
|
||
|
|
||
|
```
|
||
|
|
||
|
FC32 - N8:
|
||
|
```pascal
|
||
|
|
||
|
"ToQ4_D".FromHenkel := "ComHenkel_D".FromHenkel_L23;
|
||
|
|
||
|
"ComHenkel_D".ToHenkel.SignalExchange.Labeller."AlplaGate_L23/L24" :=
|
||
|
"FromQ4_D".ToHenkel.SignalExchange.Labeller."AlplaGate_L23/L24";
|
||
|
|
||
|
"ComHenkel_D".ToHenkel.SignalExchange.Filler :=
|
||
|
"FromQ4_D".ToHenkel.SignalExchange.Filler;
|
||
|
|
||
|
"ComHenkel_D".ToHenkel.SignalExchange.Labeller."di10.x"[8] := "FromQ4_D".ToHenkel.SignalExchange.Labeller."di10.x"[8];
|
||
|
"ComHenkel_D".ToHenkel.SignalExchange.Labeller."di10.x"[9] := "FromQ4_D".ToHenkel.SignalExchange.Labeller."di10.x"[9];
|
||
|
|
||
|
"ComHenkel_D".ToHenkel.SignalExchange.Labeller.di13 := "FromQ4_D".ToHenkel.SignalExchange.Labeller.SpeedReference;
|
||
|
```
|
||
|
|
||
|
FC9: - N10:
|
||
|
|
||
|
```pascal
|
||
|
"ToQ3_D".FromHenkel := "ComHenkel_D".FromHenkel_L23;
|
||
|
|
||
|
"ComHenkel_D".ToHenkel.SignalExchange.Labeller."di10.x"[0] := "FromQ3_D".ToHenkel.SignalExchange.Labeller."di10.x"[0];
|
||
|
"ComHenkel_D".ToHenkel.SignalExchange.Labeller."di10.x"[1] := "FromQ3_D".ToHenkel.SignalExchange.Labeller."di10.x"[1];
|
||
|
|
||
|
"ComHenkel_D".ToHenkel.SignalExchange.Labeller.SpeedReference := "FromQ3_D".ToHenkel.SignalExchange.Labeller.SpeedReference;
|
||
|
|
||
|
```
|
||
|
|
||
|
FC26 - Net 7:
|
||
|
This counters depends on which Labeler is in production:
|
||
|
|
||
|
| `"ToQ4_D".FromHenkel.SignalExchange.Labeller."di10.x"[3] = 0` | => MCC in production |
|
||
|
| -------------------------------------------------------------- | -------------------- |
|
||
|
| `"ToQ4_D".FromHenkel.SignalExchange.Labeller."di10.x"[10] = 0` | => PE in production |
|
||
|
| | |
|
||
|
|
||
|
![[Pasted image 20240408151045.png|475]]
|
||
|
|
||
|
FC6 - Net 3 :
|
||
|
|
||
|
![[Pasted image 20240403145852.png]]
|
||
|
|
||
|
#### The Q4/Q5 now will only work with L24 signals:
|
||
|
***
|
||
|
|
||
|
Depends how Henkel will manage this change.
|
||
|
|
||
|
FC32:
|
||
|
![[Pasted image 20240408144625.png]]
|
||
|
|
||
|
In the future this will be only L24 so may be HENKEL decide to transfer all info on the L24 Prosoft.
|
||
|
So we need to change to:
|
||
|
|
||
|
```
|
||
|
"ToQ4_D".FromHenkel := "ComHenkel_D".FromHenkel_L24;
|
||
|
```
|
||
|
|