#### 1. Set de IP with the BootP-DHCP Tool or the fix selectors
#### 2. Connect:
![[Pasted image 20241113143906.png|925]]
#### Start commissioning:
![[Pasted image 20241113144039.png|925]]
![[Pasted image 20241106143030.png|925]]
![[Pasted image 20241106143044.png|925]]
![[Pasted image 20241106143204.png|925]]
![[Pasted image 20241106143130.png|625]]
![[Pasted image 20241106143229.png|925]]
![[Pasted image 20241106143319.png|925]]
![[Pasted image 20241106143403.png|925]]
![[Pasted image 20241111140802.png|900]]
### Option with Analog:
0x2636:001 : 0
0x2636:002 : 20hz ( Da testare il minimo )
0x2636:003 : 120hz
![[Pasted image 20241113144249.png|900]]
### Option for Network control:
![[Pasted image 20241111144606.png|900]]
![[Pasted image 20241106143747.png|900]]
0x2631:037 : 1 ( Constant True )
0x23A1:005 : 0 ( IP Static )
![[Pasted image 20241113144544.png|900]]
#### Save parameter on Drive:
![[Pasted image 20241111150316.png|900]]
#### Restart with current values:
![[Pasted image 20241111150227.png|900]]
#### Reset:
![[Pasted image 20241111150411.png|925]]
#### Device name / Set point / Run enable:
![[Pasted image 20241119161705.png|950]]
Parameter: 0x2860:001 : (2) Analog input - To allow both controls
![[Pasted image 20241119161911.png|950]]
## Parameter to be downloaded:
![[i550 protec Network and Analog Control.gdc]]
### Important Parameters:
***
| Index | Subindex | Value | Text | Unit | Display Value |
| :----: | :------: | :-----------: | :----------------------------------------: | :--: | :----------------------: |
| 0x2001 | 0 | M23160 | Device name | | |
| 0x23A1 | 1 | 192.168.1.131 | EtherNet/IP settings: IP address | | |
| 0x23A1 | 5 | 0 | EtherNet/IP settings: IP configuration | | Stored IP [0] |
| 0x2540 | 1 | 2 | Mains settings: Rated mains voltage | | 480 Veff [2] |
| 0x2631 | 2 | 1 | Function list: Run | | Constant TRUE [1] |
| 0x2631 | 13 | 0 | Function list: Reverse rotational direct. | | Not connected [0] |
| 0x2631 | 37 | 1 | Function list: Activate network control | | Constant TRUE [1] |
| 0x2634 | 1 | 50 | Digital outputs function: Relay | | Running [50] |
| 0x2634 | 2 | 51 | Digital outputs function: Digital output 1 | | Ready for operation [51] |
| 0x2636 | 2 | 20 | Analog input 1: Min frequency value | Hz | |
| 0x2636 | 3 | 120 | Analog input 1: Max frequency value | Hz | |
| 0x2640 | 2 | 0 | HTL input settings: Maximum frequency | Hz | |
| 0x2860 | 1 | 1 | Frequency control: Default setpoint source | | Analog |
| 0x2916 | 0 | 120 | Maximum frequency | Hz | |
| 0x2917 | 0 | 3 | Acceleration time 1 | s | |
| 0x2918 | 0 | 3 | Deceleration time 1 | s | |