```pascal // Block Type: FB // Block Number: 1789 // Original Network Languages: LAD // Block Comment: // TASK1 PID FUNCTION_BLOCK "PID_RVP303" { S7_Optimized_Access := 'TRUE' } VERSION : 0.1 VAR_STAT PID_SyrLeve_Prop : Real; PID_SyrLevel_Int : Real; PID_SyrLevel_Der : Real; PID : "PIDControl"; END_VAR VAR_TEMP mMaxSyrLevel : Real; mMaxSyrLevelAnalog : Bool; END_VAR BEGIN // Network 1: Manual Enable (Original Language: LAD) "HMI_PID"."RVP303"."ManualControl"."PidEnable" := ("gCIP_SyrTank_MaxLevel" AND (("gBlenderRinseMode" AND "Procedure_Variables"."TM301_Drain"."Latch") OR ("gBlenderCIPMode" AND "gCIPRinseOpenValves" AND "CIP_Program_Variables"."Status"."CausticRecoveryRun" AND "CIP_Program_Variables"."Status"."BlenderDrainRunning"))) OR ("Blender_Variables_Pers"."gWaterRecipe" AND "gBlenderProdMode" AND "gBlenderRinseMode" AND (("gIN_SyrRoomOk" AND ("Procedure_Variables"."FTP302Line_Preparation"."Running" OR "Procedure_Variables"."FTP302_StartUp"."Running")) OR ("Procedure_Variables"."Blender_Run"."Latch" AND ("Procedure_Variables"."Syr_RunOut"."Latch" OR ("Procedure_Variables"."First_Production"."Latch" AND "Procedure_Variables"."FTP302Line_Preparation"."Done"))))); // Network 2: Setpoint (Original Language: LAD) "HMI_PID"."RVP303"."Sp" := "Blender_Variables"."gSP_SYR_Level"; // Network 3: Setpoint (Original Language: LAD) IF "gSyrTank_Loading" AND "System_RunOut_Variables"."ProdPipe_RunOut"."Running" AND (("gBlenderCIPMode" AND "HMI_PID"."RVP303"."ManualControl"."PidEnable" AND "Procedure_Variables"."Blender_Run"."Wait") OR ("System_RunOut_Variables"."FastChangeOverActivated" AND "Procedure_Variables"."FTP302Line_Preparation"."Running" AND "Procedure_Variables"."FTP302_StartUp"."Running" AND "HMI_PID"."RVP303"."ManualControl"."PidEnable" AND "Procedure_Variables"."Blender_Run"."Running")) THEN "HMI_PID"."RVP303"."Sp" := "HMI_PID"."RVP303"."Pv"; END_IF; // Network 4: PID Control (Original Language: LAD) // Attenzione al Bit REG_INV !! "PID"(D_Sel := "AUX TRUE", FF_Enable := "AUX TRUE", I_Sel := "AUX TRUE", LMN_FAC := 1.0, LMN_OFF := 0.0, MAN_ON := "HMI_PID"."RVP303"."ManualControl"."ManOut", PID_Data := "HMI_PID"."RVP303", PID_Enable := "HMI_PID"."RVP303"."ManualControl"."PidEnable" OR "HMI_PID"."RVP303"."I_ITL", P_Sel := "AUX TRUE", REG_INV := "AUX FALSE"); // Network 5: Integral PID Inizilize (Original Language: LAD) IF "HMI_PID"."RVP303"."I_ITL" THEN "HMI_PID"."RVP303"."I_ITL" := FALSE; END_IF; // Network 6: Valve Output (Original Language: LAD) "mMaxSyrLevel" := "Blender_Variables"."gSP_SYR_Level" + 10.0; "mMaxSyrLevelAnalog" := "HMI_Instrument"."LTP303"."PVFiltered" > "mMaxSyrLevel"; // Network 7: Valve Output (Original Language: LAD) SEL_R(G := "HMI_PID"."RVP303"."ManualControl"."PidEnable" AND ("HMI_PID"."RVP303"."ManualControl"."ManOut" OR "mMaxSyrLevelAnalog"), IN0 := 0.0, IN1 := "HMI_PID"."RVP303"."Out"); END_FUNCTION_BLOCK ```