{"path":"04-InLavoro/Matteo/23 - 9.3136 Sipa - Polonia Supervisore/Reporte/adjuntos/Pasted image 20240419134509.png","text":"The following settings are necessary for communication with an S7 1511 PLC: TIA: » PLC -> General -> Protection: Allow access by remote partner via PUT/GET communication: active » PLC -> Data block -> General -> Attributes: Optimized block access: Inactive zenon Driver, TCP/IP connection (on page 18) tab: » Remote TSAP: 02.01 The controller expects direct addresses, no Symbolic address.","libVersion":"0.3.1","langs":"eng+ita"}