Obsidean_VM/04-SIDEL/05 - E5.007161 - Modifica O.../SAE346 - Signals - CIP - Fi...

5.9 KiB

A60.0 : CIP REQUEST

FC2026 !Pasted image 20250409145045.png

A60.1 : CIP DRAINAGE FINISHED

FC2026 !Pasted image 20250409145620.png

A68.0 : SIRUP REQUEST

FC2026 !Pasted image 20250409150008.png

FC1870 !Pasted image 20250409150813.png

A68.1 : WATER REQUEST

!Pasted image 20250409150053.png

!Pasted image 20250409150152.png

Filler with ISO on TCP


S7 300 : FC1991: !Pasted image 20250409161646.png

FC3512 - MIXER - TIA Portal !Pasted image 20250409162237.png

MIXER FILLER
Receive DB900.DBX100.0 DB900.DBX140.0 : "Interlocking_Variables".FILLER_MIXER_RECEIVE
Send DB900.DBX140.0 DB900.DBX100.0 : "Interlocking_Variables".MIXER_FILLER_SEND

Master Tia:

    "Interlocking_Variables".MIXER_FILLER_SEND.ProdAvailableLit := REAL_TO_INT ("System_RunOut_Variables".TotalProductAvailable) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Pressure_SP := REAL_TO_INT ("HMI_Blender_Parameters".Actual_Recipe_Parameters._FillingValveHead_SP) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Pressure_PV := REAL_TO_INT ("HMI_PID".PPM303.Pv) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Tank_Level := REAL_TO_INT ("HMI_Instrument".LTM302.PVFiltered * 10 ) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Pump_Freq := REAL_TO_INT ("HMI_PID".PPM303.Out * 10 ) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Recipe_Number := BYTE_TO_INT ("System_RunOut_Variables".FillerNextRecipeNum) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Tank_Pressure_PV := REAL_TO_INT("HMI_PID".RVM301.Pv * 10);
    "Interlocking_Variables".MIXER_FILLER_SEND.Tank_Pressure_SP := REAL_TO_INT ("HMI_PID".RVM301.Sp * 10 ) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.CO2_Prod_Pressure := "P_AI_PTF203":P ;
    
    "Interlocking_Variables".MIXER_FILLER_SEND.Tank_Min_Lvl := "gOUT_FillerMinimumLevel";
    "Interlocking_Variables".MIXER_FILLER_SEND.Stop_Filler_Critical_Level := NOT "gBlenderMinLevel";
    "Interlocking_Variables".MIXER_FILLER_SEND.Alive_Bit := "AUX TRUE";
    
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_AVM362_Status := "HMI_Device".AVM362.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_AVM346_Status := "HMI_Device".AVM346.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_AVM315_Status := "HMI_Device".AVM315.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_AVM313_Status := "HMI_Device".AVM313.Out;
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_PPM303_Status := "HMI_Device".PPM303.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_PPM306_Status := "HMI_Device".PPM306.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.PROD_Press_Running := "HMI_Variables_Status".Procedures.BlendFillSysPressRun ;
    "Interlocking_Variables".MIXER_FILLER_SEND.PROD_Prod_Load := "HMI_Variables_Status".Procedures.BlendFillSysProdLoadRun ;
    "Interlocking_Variables".MIXER_FILLER_SEND.PROD_Prod_Send := "HMI_Variables_Status".Procedures.BlendFillSysProdSendRun ;
    "Interlocking_Variables".MIXER_FILLER_SEND.PROD_Product_Completed := "System_RunOut_Variables".Out_Flr_ProductCompleted ;

S7 - 300:

    "Interlocking_Variables".MIXER_FILLER_SEND.ProdAvailableLit := REAL_TO_INT ("System_RunOut_Variables".TotalProductAvailable) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Pressure_SP := REAL_TO_INT ("HMI_Blender_Parameters".Actual_Recipe_Parameters._FillingValveHead_SP) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Pressure_PV := REAL_TO_INT ("HMI_PID".PPM303.PV) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Tank_Level := REAL_TO_INT ("HMI_Instrument".LTM302.PVFiltered * 10 ) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Pump_Freq := REAL_TO_INT ("HMI_PID".PPM303.Out * 10 ) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Recipe_Number := BYTE_TO_INT ("System_RunOut_Variables".FillerNextRecipeNum) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Tank_Pressure_PV := REAL_TO_INT ("HMI_PID".RVM301.PV * 10 ) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Tank_Pressure_SP := REAL_TO_INT ("HMI_PID".RVM301.SP * 10 ) ;
    "Interlocking_Variables".MIXER_FILLER_SEND.CO2_Prod_Pressure := "AI_DifferentialTrasducer" ;     
 
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_AVM362_Status := "HMI_Device".AVM362.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_AVM346_Status := "HMI_Device".AVM346.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_AVM315_Status := "HMI_Device".AVM315.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.GEN_AVM313_Status := "HMI_Device".AVM313.Out;
    "Interlocking_Variables".MIXER_FILLER_SEND.Gen_PPM303_Status := "HMI_Device".PPM303.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.Gen_PPM306_Status := "HMI_Device".PPM306.Out ;
    "Interlocking_Variables".MIXER_FILLER_SEND.PROD_Press_Running := "HMI_Variables_Status".Procedures.BlendFillSysPressRun ;
    "Interlocking_Variables".MIXER_FILLER_SEND.PROD_Prod_Load := "HMI_Variables_Status".Procedures.BlendFillSysProdLoadRun ;
    "Interlocking_Variables".MIXER_FILLER_SEND.PROD_Prod_Send := "HMI_Variables_Status".Procedures.BlendFillSysProdSendRun ;
    "Interlocking_Variables".MIXER_FILLER_SEND.PROD_Product_Completed := "System_RunOut_Variables".Out_Flr_ProductCompleted ;
  • The master has this extra parameters:
    "Interlocking_Variables".MIXER_FILLER_SEND.Tank_Min_Lvl := "gOUT_FillerMinimumLevel";
    "Interlocking_Variables".MIXER_FILLER_SEND.Stop_Filler_Critical_Level := NOT "gBlenderMinLevel";
    "Interlocking_Variables".MIXER_FILLER_SEND.Alive_Bit := "AUX TRUE";

This bits are not present on the Master TIA software

!Pasted image 20250409164941.png

!Pasted image 20250409173420.png