General Information

This document details the differences between the factory configuration of the Endress+Hauser Promag 500DP and the specific configuration implemented for the Water system in the mixer.

Device Information

Parameter Factory Configuration Water System Configuration
Device tag Promag300/500DP Promag300/500DP
Serial number WC2C3519000 WC2C3519000
Firmware version V1.00.02 V1.00.02
Nominal diameter DN50 / 2" DN50 / 2"

Key Configuration Differences

1. Measurement Units

Parameter Factory Values Water System Values Impact
Volume flow unit l/h l/min Higher precision for real-time process control
Volume unit dm³ l More practical unit for process monitoring
Mass flow unit kg/h kg/min Consistent with volume flow time units

2. Communication and Fieldbus

Parameter Factory Values Water System Values Impact
Device address 126 20 Specific address in PROFIBUS network
Status PROFIBUS Master Config Not active Active Confirmation of active communication with PLC
PROFIBUS baudrate Not available 1.5 MBaud Specified communication speed

3. Analog Output Configuration

Parameter Factory Values Water System Values Impact
0/4 mA value (Output 1) 0.000 l/h 0.000 l/min Adjusted to system units
20 mA value (Output 1) 18000.00 l/h 200.000 l/min Range adjusted for water dosing (18000 l/h = 300 l/min)
100% bargraph value 1 18000.00 l/h 200.0000 l/min Display range consistent with operational range

4. Pulse Output Configuration

Parameter Factory Values Water System Values Impact
Value per pulse 2.5000 dm³ 1.5000 l Adjusted for more precise totalizing

5. Low Flow Cut Off

Parameter Factory Values Water System Values Impact
On value low flow cutoff 300.0000 l/h 3.0000 l/min Adjusted to eliminate noise readings when idle (300 l/h = 5 l/min)
Off value low flow cutoff 50% 50% No change

6. Totalizer Configuration

Parameter Factory Values Water System Values Impact
Unit totalizer 1 l More practical unit for process monitoring
Unit totalizer 2 l More practical unit for process monitoring
Unit totalizer 3 l More practical unit for process monitoring

7. Calibration and Adjustments

Parameter Factory Values Water System Values Impact
Calibration factor 0.7688 0.7688 No change
Zero point 5e-01 5e-01 No change
Calibration date/time 16.01.25 18:29 16.01.25 18:29 Same calibration

Signal Processing Parameters

The signal processing configuration remains unchanged between factory settings and the Water system configuration:

  • Flow damping: 4 (filter application)
  • Filter options: Binomial
  • Median filter depth: 1
  • Response time 95%: 0.5 s

These settings provide optimal noise filtering while maintaining good response characteristics.

Recommendations

  1. Flow range validation: Verify that the configured range of 0-200 l/min is appropriate for all operating conditions of the Water system.

  2. System integration verification: Confirm that the PROFIBUS address (20) is correctly recognized by the control system.

  3. Pulse output monitoring: Since the pulse output is configured to 1.5 liters per pulse, ensure that any connected systems correctly interpret this value for accurate totalization.

  4. Document future calibrations: Maintain records of any additional adjustments made to the instrument.

Conclusions

The Promag 500DP configuration for the Water system has been specifically adapted to:

  1. Work with more appropriate units for the process (l/min instead of l/h)
  2. Establish measurement ranges appropriate for water dosing (200 l/min)
  3. Configure pulse output with an appropriate value per pulse for accurate totalization
  4. Set up PROFIBUS communication with the appropriate address for the system

These changes optimize the flowmeter's performance for its specific application in the water dosing process. The signal processing parameters provide a good balance between noise filtering and response time, which is important for accurate measurements in water applications.