1 | Device tag | Serial number | Firmware version | Fieldbus Type |
---|---|---|---|---|
2 | Promag300/500DP | WC2C3519000 | V1.00.02 | 53 |
3 | MENU PATH | PARAMETER TEXT | PARAMETER VALUE | UNIT |
4 | Menu/Operation / | Web server language | English | |
5 | Menu/Operation / | Display language | English | |
6 | Menu/Operation / | Access status | Maintenance | |
7 | Menu/Operation / | Locking status | Temporarily locked | |
8 | Menu/Operation /Display / | Format display | 1 value, max. size | |
9 | Menu/Operation /Display / | Contrast display | 50 | % |
10 | Menu/Operation /Display / | Backlight | Enable | |
11 | Menu/Operation /Display / | Display interval | 5 | s |
12 | Menu/Operation /Totalizer handling/ | Control Totalizer 1 | Totalize | |
13 | Menu/Operation /Totalizer handling/ | Preset value 1 | 0.0000 | l |
14 | Menu/Operation /Totalizer handling/ | Control Totalizer 2 | Totalize | |
15 | Menu/Operation /Totalizer handling/ | Preset value 2 | 0.0000 | l |
16 | Menu/Operation /Totalizer handling/ | Control Totalizer 3 | Totalize | |
17 | Menu/Operation /Totalizer handling/ | Preset value 3 | 0.0000 | l |
18 | Menu/Operation /Totalizer handling/ | Reset all totalizers | Cancel | |
19 | Menu/Setup / | Device tag | Promag300/500DP | |
20 | Menu/Setup /System units/ | Volume flow unit | l/min | |
21 | Menu/Setup /System units/ | Volume unit | l | |
22 | Menu/Setup /System units/ | Conductivity unit | µS/cm | |
23 | Menu/Setup /System units/ | Temperature unit | °C | |
24 | Menu/Setup /System units/ | Mass flow unit | kg/min | |
25 | Menu/Setup /System units/ | Mass unit | kg | |
26 | Menu/Setup /System units/ | Density unit | kg/l | |
27 | Menu/Setup /System units/ | Corrected volume flow unit | Nl/min | |
28 | Menu/Setup /System units/ | Corrected volume unit | Nl | |
29 | Menu/Setup /Communication/ | Device address | 20 | |
30 | Menu/Setup /Analog inputs/Analog input 1/ | Channel | Volume flow | |
31 | Menu/Setup /Analog inputs/Analog input 1/ | PV filter time | 0.0000 | |
32 | Menu/Setup /Analog inputs/Analog input 1/ | Fail safe type | Fail-safe value | |
33 | Menu/Setup /Analog inputs/Analog input 1/ | Fail-safe value | 0.0000 | |
34 | Menu/Setup /Analog inputs/Analog input 2/ | Channel | Mass flow | |
35 | Menu/Setup /Analog inputs/Analog input 2/ | PV filter time | 0.0000 | |
36 | Menu/Setup /Analog inputs/Analog input 2/ | Fail safe type | Off | |
37 | Menu/Setup /Analog inputs/Analog input 3/ | Channel | Corrected volume flow | |
38 | Menu/Setup /Analog inputs/Analog input 3/ | PV filter time | 0.0000 | |
39 | Menu/Setup /Analog inputs/Analog input 3/ | Fail safe type | Off | |
40 | Menu/Setup /Analog inputs/Analog input 4/ | Channel | Flow velocity | |
41 | Menu/Setup /Analog inputs/Analog input 4/ | PV filter time | 0.0000 | |
42 | Menu/Setup /Analog inputs/Analog input 4/ | Fail safe type | Off | |
43 | Menu/Setup /I/O configuration/ | I/O module 1 terminal numbers | 26-27 (I/O 1) | |
44 | Menu/Setup /I/O configuration/ | I/O module 1 information | Profibus DP | |
45 | Menu/Setup /I/O configuration/ | I/O module 2 terminal numbers | 24-25 (I/O 2) | |
46 | Menu/Setup /I/O configuration/ | I/O module 2 information | Not configurable | |
47 | Menu/Setup /I/O configuration/ | I/O module 2 type | Current output | |
48 | Menu/Setup /I/O configuration/ | I/O module 3 terminal numbers | 22-23 (I/O 3) | |
49 | Menu/Setup /I/O configuration/ | I/O module 3 information | Not configurable | |
50 | Menu/Setup /I/O configuration/ | I/O module 3 type | Pulse/frequency/switch output | |
51 | Menu/Setup /I/O configuration/ | Alteration code | 0 | |
52 | Menu/Setup /Current output 1/ | Assign current output 1 | Volume flow | |
53 | Menu/Setup /Current output 1/ | Terminal number | 24-25 (I/O 2) | |
54 | Menu/Setup /Current output 1/ | Current span | 4...20 mA NAMUR | |
55 | Menu/Setup /Current output 1/ | Signal mode | Active | |
56 | Menu/Setup /Current output 1/ | 0/4 mA value | 0.000 | l/min |
57 | Menu/Setup /Current output 1/ | 20 mA value | 200.000 | l/min |
58 | Menu/Setup /Current output 1/ | Damping output 1 | 1.0 | s |
59 | Menu/Setup /Current output 1/ | Failure mode | Max. | |
60 | Menu/Setup /Pulse/frequency/switch output 1/ | Operating mode | Pulse | |
61 | Menu/Setup /Pulse/frequency/switch output 1/ | Terminal number | 22-23 (I/O 3) | |
62 | Menu/Setup /Pulse/frequency/switch output 1/ | Signal mode | Passive | |
63 | Menu/Setup /Pulse/frequency/switch output 1/ | Assign pulse output 1 | Volume flow | |
64 | Menu/Setup /Pulse/frequency/switch output 1/ | Value per pulse | 1.5000 | l |
65 | Menu/Setup /Pulse/frequency/switch output 1/ | Pulse width | 100.00 | ms |
66 | Menu/Setup /Pulse/frequency/switch output 1/ | Failure mode | No pulses | |
67 | Menu/Setup /Pulse/frequency/switch output 1/ | Invert output signal | No | |
68 | Menu/Setup /Display / | Value 1 display | Volume flow | |
69 | Menu/Setup /Display / | 0% bargraph value 1 | 0.0000 | l/min |
70 | Menu/Setup /Display / | 100% bargraph value 1 | 200.0000 | l/min |
71 | Menu/Setup /Display / | Value 2 display | None | |
72 | Menu/Setup /Display / | Value 3 display | None | |
73 | Menu/Setup /Display / | Value 4 display | None | |
74 | Menu/Setup /Low flow cut off/ | Assign process variable | Volume flow | |
75 | Menu/Setup /Low flow cut off/ | On value low flow cutoff | 3.0000 | l/min |
76 | Menu/Setup /Low flow cut off/ | Off value low flow cutoff | 50 | % |
77 | Menu/Setup /Low flow cut off/ | Pressure shock suppression | 0.0 | s |
78 | Menu/Setup /Empty pipe detection/ | Empty pipe detection | Off | |
79 | Menu/Setup /Advanced setup/Sensor adjustment/ | Installation direction | Flow in arrow direction | |
80 | Menu/Setup /Advanced setup/Totalizer 1/ | Assign process variable | Volume flow | |
81 | Menu/Setup /Advanced setup/Totalizer 1/ | Unit totalizer | l | |
82 | Menu/Setup /Advanced setup/Totalizer 1/ | Totalizer operation mode | Net flow total | |
83 | Menu/Setup /Advanced setup/Totalizer 1/ | Failure mode | Stop | |
84 | Menu/Setup /Advanced setup/Totalizer 2/ | Assign process variable | Volume flow | |
85 | Menu/Setup /Advanced setup/Totalizer 2/ | Unit totalizer | l | |
86 | Menu/Setup /Advanced setup/Totalizer 2/ | Totalizer operation mode | Forward flow total | |
87 | Menu/Setup /Advanced setup/Totalizer 2/ | Failure mode | Stop | |
88 | Menu/Setup /Advanced setup/Totalizer 3/ | Assign process variable | Volume flow | |
89 | Menu/Setup /Advanced setup/Totalizer 3/ | Unit totalizer | l | |
90 | Menu/Setup /Advanced setup/Totalizer 3/ | Totalizer operation mode | Reverse flow total | |
91 | Menu/Setup /Advanced setup/Totalizer 3/ | Failure mode | Stop | |
92 | Menu/Setup /Advanced setup/Display / | Decimal places 1 | x.xx | |
93 | Menu/Setup /Advanced setup/Display / | Display damping | 0.0 | s |
94 | Menu/Setup /Advanced setup/Display / | Header | Device tag | |
95 | Menu/Setup /Advanced setup/Display / | Separator | . | |
96 | Menu/Setup /Advanced setup/WLAN settings/ | WLAN | Enable | |
97 | Menu/Setup /Advanced setup/WLAN settings/ | WLAN mode | WLAN access point | |
98 | Menu/Setup /Advanced setup/WLAN settings/ | Network security | WPA2-PSK | |
99 | Menu/Setup /Advanced setup/WLAN settings/ | WLAN IP address | 192.168.1.212 | |
100 | Menu/Setup /Advanced setup/WLAN settings/ | Assign SSID name | User-defined | |
101 | Menu/Setup /Advanced setup/WLAN settings/ | SSID name | ||
102 | Menu/Setup /Advanced setup/Heartbeat setup/Heartbeat base settings/ | Plant operator | -------------------------------- | |
103 | Menu/Setup /Advanced setup/Heartbeat setup/Heartbeat base settings/ | Location | -------------------------------- | |
104 | Menu/Setup /Advanced setup/Configuration backup/ | Operating time | 0d14h56m51s | |
105 | Menu/Setup /Advanced setup/Configuration backup/ | Last backup | 0d00h00m08s | |
106 | Menu/Setup /Advanced setup/Configuration backup/ | Configuration management | Cancel | |
107 | Menu/Setup /Advanced setup/Configuration backup/ | Backup state | None | |
108 | Menu/Setup /Advanced setup/Configuration backup/ | Comparison result | Check not done | |
109 | Menu/Setup /Advanced setup/Administration/ | Device reset | Cancel | |
110 | Menu/Setup /Advanced setup/Administration/Reset access code/ | Reset access code | ||
111 | Menu/Diagnostics / | Actual diagnostics | Ok | |
112 | Menu/Diagnostics / | Previous diagnostics | Ok | |
113 | Menu/Diagnostics / | Operating time from restart | 0d03h19m50s | |
114 | Menu/Diagnostics /Diagnostic list/ | Diagnostics 1 | Ok | |
115 | Menu/Diagnostics /Diagnostic list/ | Diagnostics 2 | Ok | |
116 | Menu/Diagnostics /Diagnostic list/ | Diagnostics 3 | Ok | |
117 | Menu/Diagnostics /Diagnostic list/ | Diagnostics 4 | Ok | |
118 | Menu/Diagnostics /Diagnostic list/ | Diagnostics 5 | Ok | |
119 | Menu/Diagnostics /Event logbook/ | Filter options | All | |
120 | Menu/Diagnostics /Event logbook/ | Clear event list | Cancel | |
121 | Menu/Diagnostics /Device information / | Device tag | Promag300/500DP | |
122 | Menu/Diagnostics /Device information / | Serial number | WC2C3519000 | |
123 | Menu/Diagnostics /Device information / | Firmware version | 01.00.02 | |
124 | Menu/Diagnostics /Device information / | Device name | Promag 300 | |
125 | Menu/Diagnostics /Device information / | Order code | 5H3B50-E1R0/0 | |
126 | Menu/Diagnostics /Device information / | Extended order code 1 | 5H3B50-AAILABEFAAHDC | |
127 | Menu/Diagnostics /Device information / | Extended order code 2 | S0BA1+LP | |
128 | Menu/Diagnostics /Device information / | Extended order code 3 | ||
129 | Menu/Diagnostics /Device information / | ENP version | 2.02.00 | |
130 | Menu/Diagnostics /Device information / | PROFIBUS ident number | 0x1570 | |
131 | Menu/Diagnostics /Device information / | Status PROFIBUS Master Config | Active | |
132 | Menu/Diagnostics /Measured values /Process variables/ | Volume flow | 0.0000 | l/min |
133 | Menu/Diagnostics /Measured values /Process variables/ | Mass flow | 0.0000 | kg/min |
134 | Menu/Diagnostics /Measured values /Process variables/ | Corrected volume flow | 0.0000 | Nl/min |
135 | Menu/Diagnostics /Measured values /Process variables/ | Flow velocity | 0.0000 | m/s |
136 | Menu/Diagnostics /Measured values /Process variables/ | Density | 1.0000 | kg/l |
137 | Menu/Diagnostics /Measured values /Totalizer 1/ | Totalizer value 1 | -11.5483 | l |
138 | Menu/Diagnostics /Measured values /Totalizer 1/ | Totalizer status 1 | Good | |
139 | Menu/Diagnostics /Measured values /Totalizer 1/ | Totalizer status (Hex) 1 | 0x80 | |
140 | Menu/Diagnostics /Measured values /Totalizer 2/ | Totalizer value 2 | 1.0428 | l |
141 | Menu/Diagnostics /Measured values /Totalizer 2/ | Totalizer status 2 | Good | |
142 | Menu/Diagnostics /Measured values /Totalizer 2/ | Totalizer status (Hex) 2 | 0x80 | |
143 | Menu/Diagnostics /Measured values /Totalizer 3/ | Totalizer value 3 | -12.5911 | l |
144 | Menu/Diagnostics /Measured values /Totalizer 3/ | Totalizer status 3 | Good | |
145 | Menu/Diagnostics /Measured values /Totalizer 3/ | Totalizer status (Hex) 3 | 0x80 | |
146 | Menu/Diagnostics /Measured values /Output values/Current output 1/ | Output current 1 | 4.00 | mA |
147 | Menu/Diagnostics /Measured values /Output values/Current output 1/ | Measured current 1 | 0.09 | mA |
148 | Menu/Diagnostics /Measured values /Output values/Pulse/frequency/switch output 1/ | Pulse output 1 | 0.000 | Hz |
149 | Menu/Diagnostics /Analog inputs/Analog input 1/ | Out value | 0.0000 | |
150 | Menu/Diagnostics /Analog inputs/Analog input 1/ | Out unit text | l/min | |
151 | Menu/Diagnostics /Analog inputs/Analog input 1/ | Out status | Good | |
152 | Menu/Diagnostics /Analog inputs/Analog input 1/ | Out status | 0x80 | |
153 | Menu/Diagnostics /Analog inputs/Analog input 2/ | Out value | 0.0000 | |
154 | Menu/Diagnostics /Analog inputs/Analog input 2/ | Out unit text | kg/min | |
155 | Menu/Diagnostics /Analog inputs/Analog input 2/ | Out status | Good | |
156 | Menu/Diagnostics /Analog inputs/Analog input 2/ | Out status | 0x80 | |
157 | Menu/Diagnostics /Analog inputs/Analog input 3/ | Out value | 0.0000 | |
158 | Menu/Diagnostics /Analog inputs/Analog input 3/ | Out unit text | Nl/min | |
159 | Menu/Diagnostics /Analog inputs/Analog input 3/ | Out status | Good | |
160 | Menu/Diagnostics /Analog inputs/Analog input 3/ | Out status | 0x80 | |
161 | Menu/Diagnostics /Analog inputs/Analog input 4/ | Out value | 0.0000 | |
162 | Menu/Diagnostics /Analog inputs/Analog input 4/ | Out unit text | m/s | |
163 | Menu/Diagnostics /Analog inputs/Analog input 4/ | Out status | Good | |
164 | Menu/Diagnostics /Analog inputs/Analog input 4/ | Out status | 0x80 | |
165 | Menu/Diagnostics /Data logging/ | Data logging | Overwriting | |
166 | Menu/Diagnostics /Heartbeat/Performing verification / | Year | 10 | |
167 | Menu/Diagnostics /Heartbeat/Performing verification / | Month | January | |
168 | Menu/Diagnostics /Heartbeat/Performing verification / | Day | 1 | |
169 | Menu/Diagnostics /Heartbeat/Performing verification / | Hour | 12 | |
170 | Menu/Diagnostics /Heartbeat/Performing verification / | Minute | 0 | |
171 | Menu/Diagnostics /Heartbeat/Performing verification / | Start verification | Cancel | |
172 | Menu/Diagnostics /Heartbeat/Performing verification / | Progress | 100 | |
173 | Menu/Diagnostics /Heartbeat/Performing verification / | Status | Not done | |
174 | Menu/Diagnostics /Heartbeat/Performing verification / | Overall result | Not done | |
175 | Menu/Diagnostics /Simulation / | Assign simulation process variable | Off | |
176 | Menu/Diagnostics /Simulation / | Current output 1 simulation | Off | |
177 | Menu/Diagnostics /Simulation / | Pulse output simulation 1 | Off | |
178 | Menu/Diagnostics /Simulation / | Device alarm simulation | Off | |
179 | Menu/Diagnostics /Simulation / | Diagnostic event simulation | 65533 | |
180 | Menu/Diagnostics /Simulation / | Diagnostic event category | Process | |
181 | Menu/Diagnostics /Simulation / | Diagnostic event simulation | Off | |
182 | Menu/Expert/System/Diagnostic handling/ | Alarm delay | 0 | s |
183 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 043 | Warning | |
184 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 302 | Warning | |
185 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 376 | Warning | |
186 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 377 | Warning | |
187 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 441 | Warning | |
188 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 442 | Warning | |
189 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 443 | Warning | |
190 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 531 | Warning | |
191 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 832 | Logbook entry only | |
192 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 833 | Logbook entry only | |
193 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 834 | Warning | |
194 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 835 | Warning | |
195 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 842 | Off | |
196 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 962 | Warning | |
197 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 937 | Warning | |
198 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 938 | Alarm | |
199 | Menu/Expert/System/Diagnostic handling/Diagnostic behavior/ | Assign behavior of diagnostic no. 961 | Alarm | |
200 | Menu/Expert/System/Administration/ | Activate SW option | 385943 | |
201 | Menu/Expert/System/Administration/ | Software option overview | OPC-UA | |
202 | Menu/Expert/Sensor/System units/ | Date/time format | dd.mm.yy hh:mm | |
203 | Menu/Expert/Sensor/Process parameters/ | Filter options | Binomial | |
204 | Menu/Expert/Sensor/Process parameters/ | Flow damping | 4 | |
205 | Menu/Expert/Sensor/Process parameters/ | Median filter depth | 1 | |
206 | Menu/Expert/Sensor/Process parameters/ | Response time 95 % | 0.5 | s |
207 | Menu/Expert/Sensor/Process parameters/ | Flow override | Off | |
208 | Menu/Expert/Sensor/Process parameters/ | Conductivity measurement | Off | |
209 | Menu/Expert/Sensor/Process parameters/ | Conductivity damping | 0.00 | s |
210 | Menu/Expert/Sensor/Process parameters/ | Conductivity temperature coefficient | 2.10 | %/K |
211 | Menu/Expert/Sensor/Process parameters/ | Reference density | 1.0000 | kg/l |
212 | Menu/Expert/Sensor/External compensation/ | Density source | Fixed density | |
213 | Menu/Expert/Sensor/External compensation/ | Fixed density | 1.0000 | kg/l |
214 | Menu/Expert/Sensor/External compensation/ | Temperature source | Off | |
215 | Menu/Expert/Sensor/Sensor adjustment/ | Integration time | 20.0 | ms |
216 | Menu/Expert/Sensor/Sensor adjustment/ | Measuring period | 60.0 | ms |
217 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Volume flow offset | 0.0000 | m³/s |
218 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Volume flow factor | 1.0000 | |
219 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Mass flow offset | 0.0000 | kg/s |
220 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Mass flow factor | 1.0000 | |
221 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Conductivity offset | 0.0000 | S/m |
222 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Conductivity factor | 1.0000 | |
223 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Corrected volume flow offset | 0.0000 | Nm³/s |
224 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Corrected volume flow factor | 1.0000 | |
225 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Corrected conductivity offset | 0.0000 | S/m |
226 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Corrected conductivity factor | 1.0000 | |
227 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Flow velocity offset | 0.0000 | m/s |
228 | Menu/Expert/Sensor/Sensor adjustment/Process variable adjustment/ | Flow velocity factor | 1.0000 | |
229 | Menu/Expert/Sensor/Calibration/ | Zero point | 5e-01 | |
230 | Menu/Expert/Sensor/Calibration/ | Conductivity calibration factor | 0.7660 | |
231 | Menu/Expert/Sensor/Calibration/ | Calibration date/time | 16.01.25 18:29 | |
232 | Menu/Expert/Sensor/Calibration/Recalibration/ | Calibration factor | 1.000 | |
233 | Menu/Expert/Sensor/Calibration/Recalibration/ | Confirm settings | No | |
234 | Menu/Expert/Sensor/Calibration/Logbook/ | Calibration counter | 1 | |
235 | Menu/Expert/Sensor/Calibration/Logbook/ | Select calibration log entry | 1 | |
236 | Menu/Expert/Sensor/Calibration/Logbook/ | Timestamp | 16.01.25 18:29 | |
237 | Menu/Expert/Sensor/Calibration/Logbook/ | Calibration factor | 0.769 | |
238 | Menu/Expert/Sensor/Testpoints/ | Status | 0x30008 | |
239 | Menu/Expert/Sensor/Testpoints/ | Flow velocity | 0.0003 | m/s |
240 | Menu/Expert/Sensor/Testpoints/ | Raw volume flow | 0.0381 | l/min |
241 | Menu/Expert/Sensor/Testpoints/ | Filtered volume flow | 0.0381 | l/min |
242 | Menu/Expert/Sensor/Testpoints/ | Medium temperature | -nan | °C |
243 | Menu/Expert/Sensor/Testpoints/ | Electronic temperature | 30.1826 | °C |
244 | Menu/Expert/Sensor/Testpoints/ | Current difference potential | 0.0032 | V |
245 | Menu/Expert/Sensor/Testpoints/ | Current potential electrode 1 | -1.5581 | V |
246 | Menu/Expert/Sensor/Testpoints/ | Current potential electrode 2 | -1.5581 | V |
247 | Menu/Expert/Sensor/Testpoints/ | Current potential electrode Pipe GND | -0.0041 | V |
248 | Menu/Expert/Sensor/Testpoints/ | EPD actual value (EPD) | 0 | Ohm |
249 | Menu/Expert/Sensor/Testpoints/ | EPD actual value (E1) | 0 | Ohm |
250 | Menu/Expert/Sensor/Testpoints/ | EPD actual value (E2) | 0 | Ohm |
251 | Menu/Expert/Sensor/Testpoints/ | Current gain mode | High | |
252 | Menu/Expert/Sensor/Testpoints/ | Current measuring period | 60.02 | ms |
253 | Menu/Expert/Sensor/Testpoints/ | Current rise time | 4.6989 | ms |
254 | Menu/Expert/Sensor/Testpoints/ | Current integration time | 20.00 | ms |
255 | Menu/Expert/Sensor/Testpoints/ | Split time | 13.20 | ms |
256 | Menu/Expert/Sensor/Testpoints/ | PeakShotCoil | 97.5479 | mA |
257 | Menu/Expert/Sensor/Testpoints/ | Current shot voltage | 60.4319 | V |
258 | Menu/Expert/Sensor/Testpoints/ | Current hold voltage | 7.0051 | V |
259 | Menu/Expert/Sensor/Testpoints/ | Coil impedance | 76.8692 | Ohm |
260 | Menu/Expert/Sensor/Testpoints/ | Power line current synchronisation | Asynchronous | |
261 | Menu/Expert/Sensor/Testpoints/ | Ground connection switch | Closed | |
262 | Menu/Expert/Sensor/Properties/ | Nominal diameter | 0.0500 | m |
263 | Menu/Expert/Sensor/Properties/ | Tube inner diameter | 0.0500 | m |
264 | Menu/Expert/Sensor/Properties/ | Temperature sensor type | No | |
265 | Menu/Expert/Sensor/Properties/ | EPD electrode existing | Yes | |
266 | Menu/Expert/Sensor/Properties/ | Conductivity measurement existing | Yes | |
267 | Menu/Expert/Output /Current output 1/ | Measuring mode | Forward flow | |
268 | Menu/Expert/Output /Current output 1/ | Response time | 1.0000 | s |
269 | Menu/Expert/Output /Current output 1/ | Trim | Off | |
270 | Menu/Expert/Output /Current output 1/ | Status | 76 | |
271 | Menu/Expert/Output /Pulse/frequency/switch output 1/ | Measuring mode | Forward flow | |
272 | Menu/Expert/Communication/PROFIBUS DP configuration/ | Address mode | Software | |
273 | Menu/Expert/Communication/PROFIBUS DP configuration/ | Ident number selector | Automatic mode | |
274 | Menu/Expert/Communication/PROFIBUS DP configuration/ | Bus termination | Off | |
275 | Menu/Expert/Communication/PROFIBUS DP info/ | Profile version | 3.02 | |
276 | Menu/Expert/Communication/PROFIBUS DP info/ | Baudrate | 1.5 MBaud | |
277 | Menu/Expert/Communication/PROFIBUS DP info/ | Master availability | Yes | |
278 | Menu/Expert/Communication/Physical block / | Static revision | 1 | |
279 | Menu/Expert/Communication/Physical block / | Strategy | 0 | |
280 | Menu/Expert/Communication/Physical block / | Alert key | 0 | |
281 | Menu/Expert/Communication/Physical block / | Target mode | Auto | |
282 | Menu/Expert/Communication/Physical block / | Mode block actual | Auto | |
283 | Menu/Expert/Communication/Physical block / | Mode block permitted | 136 | |
284 | Menu/Expert/Communication/Physical block / | Mode block normal | Auto | |
285 | Menu/Expert/Communication/Physical block / | Alarm summary | 0 | |
286 | Menu/Expert/Communication/Physical block / | Software revision | 01.00.02 | |
287 | Menu/Expert/Communication/Physical block / | Hardware revision | V1.00.00 | |
288 | Menu/Expert/Communication/Physical block / | Manufacturer ID | 17 | |
289 | Menu/Expert/Communication/Physical block / | Device ID | Promag300/500DP | |
290 | Menu/Expert/Communication/Physical block / | Serial number | WC2C3519000 | |
291 | Menu/Expert/Communication/Physical block / | Diagnostics | 0 | |
292 | Menu/Expert/Communication/Physical block / | Diagnostics mask | 0 | |
293 | Menu/Expert/Communication/Physical block / | Device certification | ||
294 | Menu/Expert/Communication/Physical block / | Factory reset | Cancel | |
295 | Menu/Expert/Communication/Physical block / | Descriptor | ||
296 | Menu/Expert/Communication/Physical block / | Device message | ||
297 | Menu/Expert/Communication/Physical block / | Device install date | ||
298 | Menu/Expert/Communication/Physical block / | Hardware lock | Unprotected | |
299 | Menu/Expert/Communication/Physical block / | Feature supported | 9 | |
300 | Menu/Expert/Communication/Physical block / | Feature enabled | 9 | |
301 | Menu/Expert/Communication/Physical block / | Condensed status diagnostic | On | |
302 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 1 | 0 | |
303 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 1 | 0 | |
304 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 2 | 0 | |
305 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 2 | 0 | |
306 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 3 | 0 | |
307 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 3 | 0 | |
308 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 4 | 0 | |
309 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 4 | 0 | |
310 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 5 | 0 | |
311 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 5 | 0 | |
312 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 6 | 0 | |
313 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 6 | 0 | |
314 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 7 | 0 | |
315 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 7 | 0 | |
316 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 8 | 0 | |
317 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 8 | 0 | |
318 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 9 | 0 | |
319 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 9 | 0 | |
320 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 10 | 0 | |
321 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 10 | 0 | |
322 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 11 | 0 | |
323 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 11 | 0 | |
324 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 12 | 0 | |
325 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 12 | 0 | |
326 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 13 | 0 | |
327 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 13 | 0 | |
328 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 14 | 0 | |
329 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 14 | 0 | |
330 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 15 | 0 | |
331 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 15 | 0 | |
332 | Menu/Expert/Communication/Address shifting configuration/ | Slot shifting 16 | 0 | |
333 | Menu/Expert/Communication/Address shifting configuration/ | Index shifting 16 | 0 | |
334 | Menu/Expert/Communication/Web server/ | MAC address | 00-07-05-1C-A3-AC | |
335 | Menu/Expert/Communication/Web server/ | DHCP client | Off | |
336 | Menu/Expert/Communication/Web server/ | IP address | 192.168.1.212 | |
337 | Menu/Expert/Communication/Web server/ | Subnet mask | 255.255.255.0 | |
338 | Menu/Expert/Communication/Web server/ | Default gateway | 0.0.0.0 | |
339 | Menu/Expert/Communication/Web server/ | Web server functionality | On | |
340 | Menu/Expert/Communication/Web server/ | Login page | With header | |
341 | Menu/Expert/Communication/WLAN settings/ | WLAN MAC address | FF-FF-FF-FF-FF-FF | |
342 | Menu/Expert/Communication/WLAN settings/ | WLAN subnet mask | 255.255.255.0 | |
343 | Menu/Expert/Communication/WLAN settings/ | 2.4 GHz WLAN channel | 6 | |
344 | Menu/Expert/Communication/WLAN settings/ | Select antenna | Internal antenna | |
345 | Menu/Expert/Discrete inputs/Discrete input 1/ | Channel | Empty pipe detection | |
346 | Menu/Expert/Discrete inputs/Discrete input 1/ | Invert | Off | |
347 | Menu/Expert/Discrete inputs/Discrete input 1/ | Fail safe type | Off | |
348 | Menu/Expert/Discrete inputs/Discrete input 1/ | Out value | 0 | |
349 | Menu/Expert/Discrete inputs/Discrete input 1/ | Out status | Good | |
350 | Menu/Expert/Discrete inputs/Discrete input 1/ | Out status | 0x80 | |
351 | Menu/Expert/Discrete inputs/Discrete input 2/ | Channel | Low flow cut off | |
352 | Menu/Expert/Discrete inputs/Discrete input 2/ | Invert | Off | |
353 | Menu/Expert/Discrete inputs/Discrete input 2/ | Fail safe type | Off | |
354 | Menu/Expert/Discrete inputs/Discrete input 2/ | Out value | 1 | |
355 | Menu/Expert/Discrete inputs/Discrete input 2/ | Out status | Good | |
356 | Menu/Expert/Discrete inputs/Discrete input 2/ | Out status | 0x80 | |
357 | Menu/Expert/Analog outputs/Analog output 1/ | Set point value | 0.0000 | |
358 | Menu/Expert/Analog outputs/Analog output 1/ | Set point status | 0x18 | |
359 | Menu/Expert/Analog outputs/Analog output 1/ | Fail safe time | 0 | |
360 | Menu/Expert/Analog outputs/Analog output 1/ | Fail safe type | Off | |
361 | Menu/Expert/Analog outputs/Analog output 1/ | Out value | 0.0000 | |
362 | Menu/Expert/Analog outputs/Analog output 1/ | Out status | Bad | |
363 | Menu/Expert/Analog outputs/Analog output 1/ | Out status | 0x0 | |
364 | Menu/Expert/Analog outputs/Analog output 2/ | Set point value | 0.0000 | |
365 | Menu/Expert/Analog outputs/Analog output 2/ | Set point status | 0x18 | |
366 | Menu/Expert/Analog outputs/Analog output 2/ | Fail safe time | 0 | |
367 | Menu/Expert/Analog outputs/Analog output 2/ | Fail safe type | Off | |
368 | Menu/Expert/Analog outputs/Analog output 2/ | Out value | 0.0000 | |
369 | Menu/Expert/Analog outputs/Analog output 2/ | Out status | Bad | |
370 | Menu/Expert/Analog outputs/Analog output 2/ | Out status | 0x0 | |
371 | Menu/Expert/Discrete outputs/Discrete output 1/ | Set point value | 0 | |
372 | Menu/Expert/Discrete outputs/Discrete output 1/ | Set point status | 0x18 | |
373 | Menu/Expert/Discrete outputs/Discrete output 1/ | Invert | Off | |
374 | Menu/Expert/Discrete outputs/Discrete output 1/ | Fail safe time | 0 | |
375 | Menu/Expert/Discrete outputs/Discrete output 1/ | Fail safe type | Off | |
376 | Menu/Expert/Discrete outputs/Discrete output 1/ | Out value | 0 | |
377 | Menu/Expert/Discrete outputs/Discrete output 1/ | Out status | Bad | |
378 | Menu/Expert/Discrete outputs/Discrete output 1/ | Out status | 0x0 | |
379 | Menu/Expert/Discrete outputs/Discrete output 2/ | Set point value | 0 | |
380 | Menu/Expert/Discrete outputs/Discrete output 2/ | Set point status | 0x18 | |
381 | Menu/Expert/Discrete outputs/Discrete output 2/ | Invert | Off | |
382 | Menu/Expert/Discrete outputs/Discrete output 2/ | Fail safe time | 0 | |
383 | Menu/Expert/Discrete outputs/Discrete output 2/ | Fail safe type | Off | |
384 | Menu/Expert/Discrete outputs/Discrete output 2/ | Out value | 0 | |
385 | Menu/Expert/Discrete outputs/Discrete output 2/ | Out status | Bad | |
386 | Menu/Expert/Discrete outputs/Discrete output 2/ | Out status | 0x0 | |
387 | Menu/Expert/Discrete outputs/Discrete output 3/ | Set point value | 0 | |
388 | Menu/Expert/Discrete outputs/Discrete output 3/ | Set point status | 0x18 | |
389 | Menu/Expert/Discrete outputs/Discrete output 3/ | Invert | Off | |
390 | Menu/Expert/Discrete outputs/Discrete output 3/ | Fail safe time | 0 | |
391 | Menu/Expert/Discrete outputs/Discrete output 3/ | Fail safe type | Off | |
392 | Menu/Expert/Discrete outputs/Discrete output 3/ | Out value | 0 | |
393 | Menu/Expert/Discrete outputs/Discrete output 3/ | Out status | Bad | |
394 | Menu/Expert/Discrete outputs/Discrete output 3/ | Out status | 0x0 | |
395 | Menu/Expert/Discrete outputs/Discrete output 4/ | Set point value | 0 | |
396 | Menu/Expert/Discrete outputs/Discrete output 4/ | Set point status | 0x18 | |
397 | Menu/Expert/Discrete outputs/Discrete output 4/ | Invert | Off | |
398 | Menu/Expert/Discrete outputs/Discrete output 4/ | Fail safe time | 0 | |
399 | Menu/Expert/Discrete outputs/Discrete output 4/ | Fail safe type | Off | |
400 | Menu/Expert/Discrete outputs/Discrete output 4/ | Out value | 0 | |
401 | Menu/Expert/Discrete outputs/Discrete output 4/ | Out status | Bad | |
402 | Menu/Expert/Discrete outputs/Discrete output 4/ | Out status | 0x0 | |
403 | Menu/Expert/Discrete outputs/Discrete output 5/ | Set point value | 0 | |
404 | Menu/Expert/Discrete outputs/Discrete output 5/ | Set point status | 0x18 | |
405 | Menu/Expert/Discrete outputs/Discrete output 5/ | Invert | Off | |
406 | Menu/Expert/Discrete outputs/Discrete output 5/ | Fail safe time | 0 | |
407 | Menu/Expert/Discrete outputs/Discrete output 5/ | Fail safe type | Off | |
408 | Menu/Expert/Discrete outputs/Discrete output 5/ | Out value | 0 | |
409 | Menu/Expert/Discrete outputs/Discrete output 5/ | Out status | Bad | |
410 | Menu/Expert/Discrete outputs/Discrete output 5/ | Out status | 0x0 | |
411 | Menu/Expert/Application/Inventory counter/ | Totalizer value | 1756.149 | l |
412 | Menu/Expert/Application/Inventory counter/ | Totalizer overflow | 0 | |
413 | Menu/Expert/Application/Inventory counter/ | Unit | l | |
414 | Menu/Expert/Diagnostics /Sensor module/ | Hardware revision | V1.00.00 | |
415 | Menu/Expert/Diagnostics /Sensor module/ | Module name | Promag H | |
416 | Menu/Expert/Diagnostics /Sensor module/ | Serial number | 8031377 | |
417 | Menu/Expert/Diagnostics /Main electronic module + I/O module 1/ | Software revision | 10002 | |
418 | Menu/Expert/Diagnostics /Main electronic module + I/O module 1/ | Build no. software | 4 | |
419 | Menu/Expert/Diagnostics /Main electronic module + I/O module 1/ | Hardware revision | V1.00.00 | |
420 | Menu/Expert/Diagnostics /Main electronic module + I/O module 1/ | Module name | C302-01 | |
421 | Menu/Expert/Diagnostics /Main electronic module + I/O module 1/ | Serial number | 0354326986 | |
422 | Menu/Expert/Diagnostics /Main electronic module + I/O module 1/ | Bootloader revision | 44 | |
423 | Menu/Expert/Diagnostics /Sensor electronic module (ISEM)/ | Software revision | 10502 | |
424 | Menu/Expert/Diagnostics /Sensor electronic module (ISEM)/ | Build no. software | 0 | |
425 | Menu/Expert/Diagnostics /Sensor electronic module (ISEM)/ | Hardware revision | V1.00.00 | |
426 | Menu/Expert/Diagnostics /Sensor electronic module (ISEM)/ | Module name | V313_01 | |
427 | Menu/Expert/Diagnostics /Sensor electronic module (ISEM)/ | Serial number | 0357646111 | |
428 | Menu/Expert/Diagnostics /Sensor electronic module (ISEM)/ | Bootloader revision | 40 | |
429 | Menu/Expert/Diagnostics /I/O module 2/ | Software revision | 10001 | |
430 | Menu/Expert/Diagnostics /I/O module 2/ | Build no. software | 0 | |
431 | Menu/Expert/Diagnostics /I/O module 2/ | Hardware revision | V1.00.00 | |
432 | Menu/Expert/Diagnostics /I/O module 2/ | Module name | U300-01 | |
433 | Menu/Expert/Diagnostics /I/O module 2/ | Serial number | 0357930166 | |
434 | Menu/Expert/Diagnostics /I/O module 2/ | Bootloader revision | 10011 | |
435 | Menu/Expert/Diagnostics /I/O module 3/ | Software revision | 10001 | |
436 | Menu/Expert/Diagnostics /I/O module 3/ | Build no. software | 0 | |
437 | Menu/Expert/Diagnostics /I/O module 3/ | Hardware revision | V1.00.00 | |
438 | Menu/Expert/Diagnostics /I/O module 3/ | Module name | U300-01 | |
439 | Menu/Expert/Diagnostics /I/O module 3/ | Serial number | 0357930265 | |
440 | Menu/Expert/Diagnostics /I/O module 3/ | Bootloader revision | 10011 | |
441 | Menu/Expert/Diagnostics /Display module / | Software revision | 10108 | |
442 | Menu/Expert/Diagnostics /Display module / | Build no. software | 0 | |
443 | Menu/Expert/Diagnostics /Display module / | Hardware revision | V1.00.00 | |
444 | Menu/Expert/Diagnostics /Display module / | Module name | A300 | |
445 | Menu/Expert/Diagnostics /Display module / | Serial number | 0357438518 | |
446 | Menu/Expert/Diagnostics /Display module / | Bootloader revision | 10007 | |
447 | Menu/Expert/Diagnostics /Min/max values /Main electronic temperature/ | Minimum value | 19.0 | °C |
448 | Menu/Expert/Diagnostics /Min/max values /Main electronic temperature/ | Maximum value | 32.8 | °C |