How with the TIA Portal do you transfer your project to your operator panel via a storage medium:

https://support.industry.siemens.com/cs/document/109740696/how-with-the-tia-portal-do-you-transfer-your-project-to-your-operator-panel-via-a-storage-medium-(usb-stick-for-example)-?dti=0&lc=en-BD

Download project to storage medium

  1. Connect your storage medium (USB stick, for example) to your Engineering PC.

  2. In the project navigation in the TIA Portal you open the folder "Card Reader/USB Memory > Removable devices".

    Via the "Add user-defined Card Reader button" you can select a storage path (a folder enabled on the Runtime PC, for example) as target directory.

    !Pasted image 20240628113210.png

    Fig. 1

  3. Drag and drop the operator panel to the storage medium.

    !Pasted image 20240628113224.png

    Fig. 2

  4. Choose whether you want the user data and recipe data overwritten on the operator panel and whether this setting is to be locked on the operator panel. Click the "Load" button.


    Fig. 3

    Note: Click the operator panel in the "Devices & Networks" editor. Under PROFINET Interface > Ethernet addresses you select whether the IP address and the PROFINET device name from the project or from the device are to be used. You cannot change this setting.

A "Simatic.HMI" folder is created on the storage medium. The data is stored in this folder.

Transfer the project to Comfort / Mobile Panel

  1. Connect the storage medium to the operator panel.

  2. Open the Control Panel of the operator panel via "Settings".


    Fig. 4

  3. Double-click "Service & Commissioning".


    Fig. 5

  4. Select the "Load Project" tab and click "Next".


    Fig. 6

  5. Select the storage medium and click "Next".


    Fig. 7

  6. Select the project to be transferred and click "Next".


    Fig. 8

  7. As required you set whether the user data and recipe data is to be overwritten and whether the operator panel image is to be transferred.
    Start the download via "Load".


    Fig. 9

Transfer project to Basic Panel

  1. Connect the storage medium with the operator panel.

  2. Open the Control Panel of the operator panel via "Settings".


    Fig. 10

  3. Click "Service & Commissioning".


    Fig. 11

  4. Click "Project Download".


    Fig. 12

  5. Select the storage medium and click the arrow.


    Fig. 13

  6. Select the project and click the arrow.


    Fig. 14

  7. As required you set whether you want the user data and recipe data overwritten on the operator panel and whether the operator panel image is to be transferred. Click the arrow.


    Fig. 15

  8. Check the settings and start the download with "Accept".


    Fig. 16

Transfer project to PC

  1. Connect the storage medium with the Runtime PC

  2. Copy the files to the folder "Simatic.HMI > RT_Projects > Project_name.PCName"


    Fig. 17

  3. Open the WinCC Runtime Loader via "Start > All Programs > Siemens Automation > Runtime Systems > WinCC Runtime Advanced > WinCC Runtime Loader".
    Click the "Settings" button.


    Fig. 18

  4. Open or create the path under "Configuration path" in the Windows Explorer.
    You can also change the path as you wish.


    Fig. 19

  5. Insert the copied files into that folder.