(* @PATH := '\/Danfoss FC' *) TYPE FC_Control_Word STRUCT B00_RefValue_LSB : BOOL ; (* Choose between the four reference values, which are pre-programmed in par.3-10 *) B01_RefValue_MSB : BOOL ; B02_Brake : BOOL ; (* Bit 02 = 0 leads to DC braking and stop. Bit 02 = 1 leads to ramping. *) B03_Coast : BOOL ; (* Bit 03 = 0 causes the frequency converter to immediately "let go" of the motor, so that it coasts to a standstill. Bit 03 = 1 enables the frequency converter to start the motor if the other starting conditions have been fulfilled. *) B04_QuickStop : BOOL ; (* Bit 04 = 0 causes a stop, in which the motor speed is ramped down to stop via par. 3-81. *) B05_HoldOutputFrequency : BOOL ; (* Bit 05 = 0 causes the present output frequency (in Hz) to freeze. *) B06_RampStop : BOOL ; (* Bit 06 = 0 causes a stop, in which the motor speed is ramped down to stop via the selected ramp down parameter. Bit 06 = 1 permits the frequency converter to start the motor, if the other starting conditions have been fulfilled. *) B07_Reset : BOOL ; (* Reset of a trip is activated on the signal’s leading edge, i.e. when changing from logic "0" to logic "1". *) B08_Jog : BOOL ; (* Bit 08 = 1 causes the output frequency to be determined by par. 3-19. *) B09_RampSelection : BOOL ; (* Bit 09 = 0 means that ramp 1 is active (parameters 3-40 to 3-47). Bit 09 = 1 means that ramp 2 (par. 3-50 to 3-57) is active.*) B10_DataValid : BOOL ; (* Bit 10 = 0 causes the control word to be ignored, Bit 10 = 1 causes the control word to be used. *) B11_Relay01Active : BOOL ; (* Bit 11 = 1 Relay 01 activated, provided Control word bit 11 has been chosen in par. 5-40.*) B12_Relay04Active : BOOL ; (* Bit 12 = 1 Relay 04 activated, provided Control word bit 12 has been chosen in par. 5-40.*) B13_SetUp_LSB : BOOL ; (* Choose between the four menu set-ups, only possible when Multi-Set-ups is selected in par. 0-10. *) B14_SetUp_MSB : BOOL ; B15_Reverse : BOOL ; END_STRUCT END_TYPE (* @END_DECLARATION := '0' *)