FUNCTION "1032_FC Manual function" : Void
|
|
{ S7_Optimized_Access := 'TRUE' }
|
|
VERSION : 0.1
|
|
VAR_TEMP
|
|
wPosition : Word;
|
|
xrtCurrentLimit : Bool;
|
|
g : Int;
|
|
p : Int;
|
|
m : Int;
|
|
b : Int;
|
|
END_VAR
|
|
|
|
|
|
BEGIN
|
|
|
|
#g := "DB HMI_1".nGWNumber;
|
|
#p := "DB HMI_1".nPortNumber;
|
|
#b := "DB HMI_1".nBoxNumber;
|
|
#m := "DB HMI_1".nMotorNumber;
|
|
|
|
"rtMotInPos"(CLK:="DB HMI_1".xMotStatInPos );
|
|
|
|
IF "DB Cycle".Man THEN
|
|
|
|
// Run Forward
|
|
IF "DB HMI_1".xPBMotMoveFw AND
|
|
"DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].xEnable THEN
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Sign := TRUE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].PosType := FALSE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Position := "DB HMI_1".nPosition;
|
|
END_IF;
|
|
|
|
// Run Backward
|
|
IF "DB HMI_1".xPBMotMoveBw AND
|
|
"DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].xEnable THEN
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Sign := FALSE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].PosType := FALSE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Position := "DB HMI_1".nPosition;
|
|
END_IF;
|
|
|
|
// Run Zero/Position
|
|
IF "DB HMI_1".xPBMotMoveZeroPos AND
|
|
"DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].xEnable THEN
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].PosType := TRUE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Position := "DB HMI_1".nPosition;
|
|
END_IF;
|
|
|
|
// Stop
|
|
IF NOT "DB Cycle".xZona_MoveManFw AND NOT "DB Cycle".xZona_MoveManBw THEN
|
|
IF "DB HMI_1".xPBMotStop OR "rtMotInPos".Q OR "DB HMI_1".xMotStatAlarm THEN
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Position := 0;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].PosType := FALSE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Reset := FALSE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Sign := FALSE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Stop := FALSE;
|
|
END_IF;
|
|
IF ("DB HMI_1".xPBMotMoveFw OR "DB HMI_1".xPBMotMoveBw OR "DB HMI_1".xPBMotMoveZeroPos) AND
|
|
"DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].xEnable THEN
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Stop := TRUE;
|
|
END_IF;
|
|
END_IF;
|
|
|
|
END_IF;
|
|
|
|
// Alarm Reset
|
|
IF "DB HMI_1".xPBMotAlarmReset AND "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].MotorStatus[#m].Alarm THEN
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Reset := TRUE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Stop := TRUE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Sign := FALSE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].PosType := FALSE;
|
|
END_IF;
|
|
|
|
"rtPB_MotAlmReset"(CLK:= NOT "DB HMI_1".xPBMotAlarmReset);
|
|
|
|
IF "rtPB_MotAlmReset".Q THEN
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Reset := FALSE;
|
|
"DB Gateway".N[#g].write.P[#p].MotorBoxCtrl[#b].Mot[#m].Stop := FALSE;
|
|
END_IF;
|
|
|
|
|
|
// Motor Current limitation
|
|
"rtPB_CurrentLimit"(CLK:="DB HMI_1".xPopUpCurrentLim,
|
|
Q=>#xrtCurrentLimit);
|
|
IF "rtPB_CurrentLimit".Q THEN
|
|
"DB HMI_1".snCurrentLimFW := "DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].CurrentLimFW;
|
|
"DB HMI_1".snCurrentLimBW := "DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].CurrentLimBW;
|
|
END_IF;
|
|
IF "DB HMI_1".xPopUpCurrentLim AND NOT "rtPB_CurrentLimit".Q THEN
|
|
"DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].CurrentLimFW := "DB HMI_1".snCurrentLimFW;
|
|
"DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].CurrentLimBW := "DB HMI_1".snCurrentLimBW;
|
|
END_IF;
|
|
IF NOT "DB HMI_1".xPopUpCurrentLim THEN
|
|
"DB HMI_1".snCurrentLimFW := 0;
|
|
"DB HMI_1".snCurrentLimBW := 0;
|
|
END_IF;
|
|
|
|
// HMI Motor Status
|
|
"DB HMI_1".snGatewayFirmware := "DB Gateway".N[#g].read.P[#p].Firmware;
|
|
"DB HMI_1".nBoxInstalled := USINT_TO_INT ("DB Gateway".N[#g].read.P[#p].MboxNumber);
|
|
"DB HMI_1".snBoxFirmwareVersion := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].BoxStatus.FirmwareVersion;
|
|
"DB HMI_1".snBoxFirmwareRevision := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].BoxStatus.FirmwareRevision;
|
|
"DB HMI_1".xBox_MotEnabled := "DB MotorPar".GW[#g].P[#p].Box[#b].Mot[#m].xEnable;
|
|
"DB HMI_1".xMotStatRunningFw := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].MotorStatus[#m].MovingFW;
|
|
"DB HMI_1".xMotStatRunningBw := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].MotorStatus[#m].MovingBW;
|
|
"DB HMI_1".xMotStatInPos := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].MotorStatus[#m].InPOS;
|
|
"DB HMI_1".xMotStatAlarm := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].MotorStatus[#m].Alarm;
|
|
"DB HMI_1".xMotStatInZeroPos := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].MotorStatus[#m].InZero;
|
|
"DB HMI_1".xMotStatRunningSlowly := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].MotorStatus[#m].MovingSlowly;
|
|
"DB HMI_1".xBoxFuseBurned := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].BoxStatus.BurnedFuse;
|
|
"DB HMI_1".xBoxUndervoltage := "DB Gateway".N[#g].read.P[#p].MotorsBoxStatus[#b].BoxStatus.Undervoltage;
|
|
IF ("DB HMI_1".xMotStatRunningFw OR "DB HMI_1".xMotStatRunningBw) AND "DB Cycle".Man THEN
|
|
"DB HMI_1".xMotStatRunning := 1;
|
|
ELSE
|
|
"DB HMI_1".xMotStatRunning := 0;
|
|
END_IF;
|
|
END_FUNCTION
|
|
|