#AnelloArea #azzionamenti_neumatici #axionamentos_neumaticos #guias_neumaticas
#EMD #AIRring #potenciometros #potenciometer #g120c
## Project: [16 - AIR TEST](file:///C:%5CTrabajo%5CVM%5C16%20-%20AIR%20TEST)
### Data:
***
* 2.2kw
*
### Followed normal setup:
***
![[Pasted image 20240130154750.png]]
![[Pasted image 20240130155443.png]]
![[Pasted image 20240130155608.png]]
![[Pasted image 20240130155922.png|475]]
![[Pasted image 20240130160019.png]]
Application class:
Application class: [1] Standard Drive Control (SDC)
Setpoint specification:
Drive without PLC connection. Setpoint specification in the drive
Defaults of the setpoints/command sources:
Macro drive unit: [12] Standard I/O with analog setpoint
Drive setting:
IEC/NEMA mot stds: [0] IEC-Motor (50 Hz, SI units)
Drive unit line supply voltage: 400 V
Drive options:
Braking resistor active: No
Drive filter type motor side: [0] No filter
Motor:
Motor type selection: [1] Induction motor
Motor connection type: Star
Motor 87 Hz operation: No
Rated motor voltage: 400 Vrms
Rated motor current: 4.35 Arms
Rated motor power: 2.20 kW
Rated motor frequency: 50.00 Hz
Rated motor speed: 2895.0 rpm
Motor cooling type: [0] Natural ventilation
Motor temperature sensor type: [0] No sensor
Motor holding brake:
Motor holding brake configuration: [0] No motor holding brake available
Important parameters:
Current limit: 6.52 Arms
Minimum speed: 870.000 rpm
Maximum speed: 4340.000 rpm
Ramp-function generator ramp-up time: 5.000 s
Ramp-function generator ramp-down time: 5.000 s
OFF3 ramp-down time: 3.000 s
Drive functions:
Technological application (Standard Drive Control): [0] Constant load (linear characteristic)
Motor data identification and rotating measurement: [2] Identifying motor data (at standstill)
![[Pasted image 20240130155129.png]]
![[Pasted image 20240130155218.png|500]]
![[foto.jpg]]
#### Potentiometer 3US12:
***
![[20240130_154221.jpg|450]]
![[Pasted image 20240130162442.png]]
![[Pasted image 20240130162456.png]]
### Parameters changes after the setup:
***
#### For automatic Restart on Siemens G120C:
****
P1210 = 6
* p1210 = 6: An automatic restart is carried out if any fault has occurred.
p840 = 1
* Sets the signal source for the command "ON/OFF (OFF1)"
20-55