#AnelloArea #azzionamenti_neumatici #axionamentos_neumaticos #guias_neumaticas
|
||
|
|
||
|
#EMD #AIRring #potenciometros #potenciometer #g120c
|
||
|
|
||
|
## Project: [16 - AIR TEST](file:///C:%5CTrabajo%5CVM%5C16%20-%20AIR%20TEST)
|
||
|
|
||
|
### Data:
|
||
|
***
|
||
|
* 2.2kw
|
||
|
*
|
||
|
|
||
|
### Followed normal setup:
|
||
|
***
|
||
|
|
||
|
![[Pasted image 20240130154750.png]]
|
||
|
|
||
|
![[Pasted image 20240130155443.png]]
|
||
|
|
||
|
![[Pasted image 20240130155608.png]]
|
||
|
|
||
|
![[Pasted image 20240130155922.png|475]]
|
||
|
|
||
|
![[Pasted image 20240130160019.png]]
|
||
|
|
||
|
Application class:
|
||
|
Application class: [1] Standard Drive Control (SDC)
|
||
|
|
||
|
Setpoint specification:
|
||
|
Drive without PLC connection. Setpoint specification in the drive
|
||
|
|
||
|
Defaults of the setpoints/command sources:
|
||
|
Macro drive unit: [12] Standard I/O with analog setpoint
|
||
|
|
||
|
Drive setting:
|
||
|
IEC/NEMA mot stds: [0] IEC-Motor (50 Hz, SI units)
|
||
|
Drive unit line supply voltage: 400 V
|
||
|
|
||
|
Drive options:
|
||
|
Braking resistor active: No
|
||
|
Drive filter type motor side: [0] No filter
|
||
|
|
||
|
Motor:
|
||
|
Motor type selection: [1] Induction motor
|
||
|
Motor connection type: Star
|
||
|
Motor 87 Hz operation: No
|
||
|
Rated motor voltage: 400 Vrms
|
||
|
Rated motor current: 4.35 Arms
|
||
|
Rated motor power: 2.20 kW
|
||
|
Rated motor frequency: 50.00 Hz
|
||
|
Rated motor speed: 2895.0 rpm
|
||
|
Motor cooling type: [0] Natural ventilation
|
||
|
Motor temperature sensor type: [0] No sensor
|
||
|
|
||
|
Motor holding brake:
|
||
|
Motor holding brake configuration: [0] No motor holding brake available
|
||
|
|
||
|
Important parameters:
|
||
|
Current limit: 6.52 Arms
|
||
|
Minimum speed: 870.000 rpm
|
||
|
Maximum speed: 4340.000 rpm
|
||
|
Ramp-function generator ramp-up time: 5.000 s
|
||
|
Ramp-function generator ramp-down time: 5.000 s
|
||
|
OFF3 ramp-down time: 3.000 s
|
||
|
|
||
|
Drive functions:
|
||
|
Technological application (Standard Drive Control): [0] Constant load (linear characteristic)
|
||
|
Motor data identification and rotating measurement: [2] Identifying motor data (at standstill)
|
||
|
|
||
|
|
||
|
![[Pasted image 20240130155129.png]]
|
||
|
![[Pasted image 20240130155218.png|500]]
|
||
|
|
||
|
![[foto.jpg]]
|
||
|
|
||
|
#### Potentiometer 3US12:
|
||
|
***
|
||
|
|
||
|
![[20240130_154221.jpg|450]]
|
||
|
|
||
|
![[Pasted image 20240130162442.png]]
|
||
|
|
||
|
![[Pasted image 20240130162456.png]]
|
||
|
|
||
|
|
||
|
### Parameters changes after the setup:
|
||
|
***
|
||
|
|
||
|
#### For automatic Restart on Siemens G120C:
|
||
|
****
|
||
|
P1210 = 6
|
||
|
* p1210 = 6: An automatic restart is carried out if any fault has occurred.
|
||
|
|
||
|
p840 = 1
|
||
|
* Sets the signal source for the command "ON/OFF (OFF1)"
|
||
|
|
||
|
20-55
|
||
|
|
||
|
|
||
|
### Aggiornamento 2024:
|
||
|
***
|
||
|
|
||
|