2.4 KiB
#AnelloArea #azzionamenti_neumatici #axionamentos_neumaticos #guias_neumaticas
#EMD #AIRring #potenciometros #potenciometer #g120c
Project: 16 - AIR TEST
Data:
- 2.2kw
Followed normal setup:
!Pasted image 20240130155922.png
Application class: Application class: [1] Standard Drive Control (SDC)
Setpoint specification: Drive without PLC connection. Setpoint specification in the drive
Defaults of the setpoints/command sources: Macro drive unit: [12] Standard I/O with analog setpoint
Drive setting: IEC/NEMA mot stds: [0] IEC-Motor (50 Hz, SI units) Drive unit line supply voltage: 400 V
Drive options: Braking resistor active: No Drive filter type motor side: [0] No filter
Motor: Motor type selection: [1] Induction motor Motor connection type: Star Motor 87 Hz operation: No Rated motor voltage: 400 Vrms Rated motor current: 4.35 Arms Rated motor power: 2.20 kW Rated motor frequency: 50.00 Hz Rated motor speed: 2895.0 rpm Motor cooling type: [0] Natural ventilation Motor temperature sensor type: [0] No sensor
Motor holding brake: Motor holding brake configuration: [0] No motor holding brake available
Important parameters: Current limit: 6.52 Arms Minimum speed: 870.000 rpm Maximum speed: 4340.000 rpm Ramp-function generator ramp-up time: 5.000 s Ramp-function generator ramp-down time: 5.000 s OFF3 ramp-down time: 3.000 s
Drive functions: Technological application (Standard Drive Control): [0] Constant load (linear characteristic) Motor data identification and rotating measurement: [2] Identifying motor data (at standstill)
!
!Pasted image 20240130155218.png
Potentiometer 3US12:
Parameters changes after the setup:
For automatic Restart on Siemens G120C:
P1210 = 6
- p1210 = 6: An automatic restart is carried out if any fault has occurred.
p840 = 1
- Sets the signal source for the command "ON/OFF (OFF1)"
20-55