Obsidean_VM/03-Revised/AIR Test Cabinet - Anello A.../Notes G120 Setup for autost...

2.4 KiB

#AnelloArea #azzionamenti_neumatici #axionamentos_neumaticos #guias_neumaticas

#EMD #AIRring #potenciometros #potenciometer #g120c

Project: 16 - AIR TEST

Data:


  • 2.2kw

Followed normal setup:


!Pasted image 20240130154750.png

!Pasted image 20240130155443.png

!Pasted image 20240130155608.png

!Pasted image 20240130155922.png

!Pasted image 20240130160019.png

Application class: Application class: [1] Standard Drive Control (SDC)

Setpoint specification: Drive without PLC connection. Setpoint specification in the drive

Defaults of the setpoints/command sources: Macro drive unit: [12] Standard I/O with analog setpoint

Drive setting: IEC/NEMA mot stds: [0] IEC-Motor (50 Hz, SI units) Drive unit line supply voltage: 400 V

Drive options: Braking resistor active: No Drive filter type motor side: [0] No filter

Motor: Motor type selection: [1] Induction motor Motor connection type: Star Motor 87 Hz operation: No Rated motor voltage: 400 Vrms Rated motor current: 4.35 Arms Rated motor power: 2.20 kW Rated motor frequency: 50.00 Hz Rated motor speed: 2895.0 rpm Motor cooling type: [0] Natural ventilation Motor temperature sensor type: [0] No sensor

Motor holding brake: Motor holding brake configuration: [0] No motor holding brake available

Important parameters: Current limit: 6.52 Arms Minimum speed: 870.000 rpm Maximum speed: 4340.000 rpm Ramp-function generator ramp-up time: 5.000 s Ramp-function generator ramp-down time: 5.000 s OFF3 ramp-down time: 3.000 s

Drive functions: Technological application (Standard Drive Control): [0] Constant load (linear characteristic) Motor data identification and rotating measurement: [2] Identifying motor data (at standstill)

!Pasted image 20240130155129.png !Pasted image 20240130155218.png

!foto.jpg

Potentiometer 3US12:


!20240130_154221.jpg

!Pasted image 20240130162442.png

!Pasted image 20240130162456.png

Parameters changes after the setup:


For automatic Restart on Siemens G120C:


P1210 = 6

  • p1210 = 6: An automatic restart is carried out if any fault has occurred.

p840 = 1

  • Sets the signal source for the command "ON/OFF (OFF1)"

20-55

Aggiornamento 2024:


!20240628_131621.jpg