13 lines
690 B
Markdown
13 lines
690 B
Markdown
|
|
https://www.plctalk.net/threads/danfoss-vlt-fc302-back-to-default-factory-settings-using-keypad.67162/
|
|
|
|
* The parameter is ==1422 under group 14 (special functions) and needs to be changed from (0) to (2) then the power needs to be cycled==.
|
|
* With buttons:
|
|
* I found plenty of google references to '3 finger reset' for Danfoss FC 302 drives but couldnt find any info on ==which 3 buttons need pressing.==
|
|
* Here is the procedure :
|
|
- With the drive powered off to begin with, press and hold Status, Main Menu, and OK.
|
|
- Power up the drive, and let go of the 3 buttons when you hear the 'click'. The display will go off and on again, and A80 will be on the display then.
|
|
|
|
|
|
|