# PROFIBUS Communication with Siemens S7-1500 PLC: Implementation Guide
|
|
|
|
## 1. Introduction
|
|
|
|
This document serves as a technical reference for configuring and programming a Siemens S7-1500 PLC to communicate with PROFIBUS devices, with a specific focus on devices using a GSD file configured with 4 blocks of 32 bytes each for input and output data transfer. The document assumes the reader has basic knowledge of TIA Portal and PLC programming.
|
|
|
|
## 2. PROFIBUS Configuration Overview
|
|
|
|
### 2.1 GSD Configuration
|
|
|
|
The GSD (General Station Description) file for this implementation is configured with:
|
|
|
|
- 4 blocks of 32 bytes each for input (total 128 bytes)
|
|
- 4 blocks of 32 bytes each for output (total 128 bytes)
|
|
|
|
This configuration allows consistent data exchange between the S7-1500 PLC (master) and the PROFIBUS device (slave).
|
|
|
|
### 2.2 Hardware Requirements
|
|
|
|
- Siemens S7-1500 PLC with CM 1542-5 or CP 1542-5 PROFIBUS interface
|
|
- TIA Portal V16 or later
|
|
- GSD file for the PROFIBUS device
|
|
- PROFIBUS cable and connectors
|
|
|
|
## 3. TIA Portal Configuration
|
|
|
|
### 3.1 Importing the GSD File
|
|
|
|
1. Open TIA Portal and your project
|
|
2. Navigate to "Options" → "Manage general station description files (GSD)"
|
|
3. Click "Install" and select the GSD file for your device
|
|
4. Click "Install" and close the dialog
|
|
|
|
### 3.2 Hardware Configuration
|
|
|
|
1. Open the device configuration view
|
|
2. Add your S7-1500 CPU to the project if not already present
|
|
3. From the hardware catalog, select "PROFIBUS DP" → "Additional Field Devices" → find your device
|
|
4. Add the PROFIBUS device to the PROFIBUS network
|
|
5. Configure the PROFIBUS address (must be unique on the network)
|
|
6. Select the proper I/O configuration (4 blocks x 32 bytes for inputs and outputs)
|
|
7. Compile and download the hardware configuration
|
|
|
|
### 3.3 Setting PROFIBUS Parameters
|
|
|
|
1. Select the PROFIBUS interface of your S7-1500 PLC
|
|
2. Set the PROFIBUS address (typically 2, as 0 is reserved for programming devices and 1 often for master devices)
|
|
3. Configure the operating mode as "DP master"
|
|
4. Set the transmission rate (usually 1.5 Mbps, but ensure it matches all devices)
|
|
5. Set the highest station address (HSA) to cover all planned device addresses
|
|
|
|
## 4. Data Structure Organization
|
|
|
|
### 4.1 Input Data Structure (Device to PLC)
|
|
|
|
The 128 bytes of input data is organized in 4 blocks of 32 bytes each. Based on the provided documentation, a typical structure might be:
|
|
|
|
#### Block 1 (Bytes 0-31)
|
|
|
|
```
|
|
Byte 0: Status mPDS 5 (0=Initialization, 1=OK, 2=Warning, 4=Error)
|
|
Byte 1: Not used
|
|
Byte 2-3: Production line status
|
|
Byte 4-5: Product number (0-65535)
|
|
Byte 6-7: Product type number
|
|
Byte 8-11: Requested parameter 1 (Real)
|
|
Byte 12-15: Requested parameter 2 (Real)
|
|
Byte 16-19: Requested parameter 3 (Real)
|
|
Byte 20-23: Requested parameter 4 (Real)
|
|
Byte 24-27: Measurement value 1 (Real)
|
|
Byte 28-31: Measurement value 2 (Real)
|
|
```
|
|
|
|
#### Block 2 (Bytes 32-63)
|
|
|
|
```
|
|
Byte 32-35: Measurement value 3 (Real)
|
|
Byte 36-39: Measurement value 4 (Real)
|
|
Byte 40-43: Measurement value 5 (Real)
|
|
Byte 44-47: Measurement value 6 (Real)
|
|
Byte 48-51: Measurement value 7 (Real)
|
|
Byte 52-55: Measurement value 8 (Real)
|
|
Byte 56-59: Measurement value 9 (Real)
|
|
Byte 60-63: Measurement value 10 (Real)
|
|
```
|
|
|
|
#### Block 3 (Bytes 64-95)
|
|
|
|
```
|
|
Byte 64-67: Measurement value 11 (Real)
|
|
Byte 68-71: Measurement value 12 (Real)
|
|
Byte 72-75: Measurement value 13 (Real)
|
|
Byte 76-79: Measurement value 14 (Real)
|
|
Byte 80-83: Measurement value 15 (Real)
|
|
Byte 84-87: Measurement value 16 (Real)
|
|
Byte 88-91: Measurement value 17 (Real)
|
|
Byte 92-95: Measurement value 18 (Real)
|
|
```
|
|
|
|
#### Block 4 (Bytes 96-127)
|
|
|
|
```
|
|
Byte 96-99: Measurement value 19 (Real)
|
|
Byte 100-103: Measurement value 20 (Real)
|
|
Byte 104-107: Measurement value 21 (Real)
|
|
Byte 108-111: Measurement value 22 (Real)
|
|
Byte 112-115: Measurement value 23 (Real)
|
|
Byte 116-119: Measurement value 24 (Real)
|
|
Byte 120-123: Measurement value 25 (Real)
|
|
Byte 124-127: Measurement value 26 (Real)
|
|
```
|
|
|
|
### 4.2 Output Data Structure (PLC to Device)
|
|
|
|
The 128 bytes of output data is also organized in 4 blocks of 32 bytes each:
|
|
|
|
#### Block 1 (Bytes 0-31)
|
|
|
|
```
|
|
Byte 0-1: Product number (Word)
|
|
Byte 2-3: DI1-DI16 from PLC (16 bits)
|
|
Byte 4: Type of requested parameter 1
|
|
Byte 5: Index of requested parameter 1
|
|
Byte 6: Type of requested parameter 2
|
|
Byte 7: Index of requested parameter 2
|
|
Byte 8: Type of requested parameter 3
|
|
Byte 9: Index of requested parameter 3
|
|
Byte 10: Type of requested parameter 4
|
|
Byte 11: Index of requested parameter 4
|
|
Byte 12-13: "Enter" command for requested parameters
|
|
Byte 14-17: Measurement value 1 from PLC (Real) - Optional
|
|
Byte 18-21: Measurement value 2 from PLC (Real) - Optional
|
|
Byte 22-25: Measurement value 3 from PLC (Real) - Optional
|
|
Byte 26-29: Measurement value 4 from PLC (Real) - Optional
|
|
Byte 30-31: Type and index of parameter 1 to transfer
|
|
```
|
|
|
|
#### Block 2 (Bytes 32-63)
|
|
|
|
```
|
|
Byte 32-35: Value of parameter 1 to transfer (Real)
|
|
Byte 36-37: Type and index of parameter 2 to transfer
|
|
Byte 38-41: Value of parameter 2 to transfer (Real)
|
|
Byte 42-43: Type and index of parameter 3 to transfer
|
|
Byte 44-47: Value of parameter 3 to transfer (Real)
|
|
Byte 48-49: Type and index of parameter 4 to transfer
|
|
Byte 50-53: Value of parameter 4 to transfer (Real)
|
|
Byte 54-55: Type and index of parameter 5 to transfer
|
|
Byte 56-59: Value of parameter 5 to transfer (Real)
|
|
Byte 60-63: Type and index of parameter 6 to transfer
|
|
```
|
|
|
|
#### Block 3 (Bytes 64-95)
|
|
|
|
```
|
|
Byte 64-67: Value of parameter 6 to transfer (Real)
|
|
Byte 68-69: Type and index of parameter 7 to transfer
|
|
Byte 70-73: Value of parameter 7 to transfer (Real)
|
|
Byte 74-75: Type and index of parameter 8 to transfer
|
|
Byte 76-79: Value of parameter 8 to transfer (Real)
|
|
Byte 80-81: Type and index of parameter 9 to transfer
|
|
Byte 82-85: Value of parameter 9 to transfer (Real)
|
|
Byte 86-87: Type and index of parameter 10 to transfer
|
|
Byte 88-91: Value of parameter 10 to transfer (Real)
|
|
Byte 92-93: Type and index of parameter 11 to transfer
|
|
Byte 94-95: Beginning of value of parameter 11
|
|
```
|
|
|
|
#### Block 4 (Bytes 96-127)
|
|
|
|
```
|
|
Byte 96-97: Remaining bytes of parameter 11 value
|
|
Byte 98-99: Type and index of parameter 12 to transfer
|
|
Byte 100-103: Value of parameter 12 to transfer
|
|
Byte 104-105: Type and index of parameter 13 to transfer
|
|
Byte 106-109: Value of parameter 13 to transfer
|
|
Byte 110-111: Type and index of parameter 14 to transfer
|
|
Byte 112-115: Value of parameter 14 to transfer
|
|
Byte 116-117: Type and index of parameter 15 to transfer
|
|
Byte 118-121: Value of parameter 15 to transfer
|
|
Byte 122-125: Type and index of parameter 16 to transfer
|
|
Byte 126-127: "Enter" command for parameters to be transferred
|
|
```
|
|
|
|
## 5. TIA Portal Implementation
|
|
|
|
### 5.1 Creating Data Blocks
|
|
|
|
For better organization, create the following data blocks (DBs):
|
|
|
|
1. **DB_PROFIBUS_Config**: For configuration parameters
|
|
2. **DB_PROFIBUS_Input**: For storing input data from the device
|
|
3. **DB_PROFIBUS_Output**: For preparing output data to the device
|
|
4. **DB_PROFIBUS_Parameters**: For parameter management
|
|
|
|
#### Sample DB_PROFIBUS_Input Structure
|
|
|
|
```
|
|
// Block 1
|
|
"Status_mPDS" : Byte // Status byte
|
|
"NotUsed" : Byte // Not used
|
|
"ProductionLineStatus" : Word // Status of production line
|
|
"ProductNumber" : Word // Current product number
|
|
"ProductTypeNumber" : Word // Product type number
|
|
"RequestedParam1" : Real // Requested parameter 1
|
|
"RequestedParam2" : Real // Requested parameter 2
|
|
"RequestedParam3" : Real // Requested parameter 3
|
|
"RequestedParam4" : Real // Requested parameter 4
|
|
"MeasValue1" : Real // Measurement value 1
|
|
"MeasValue2" : Real // Measurement value 2
|
|
|
|
// Continue for all measurement values through Block 4
|
|
```
|
|
|
|
#### Sample DB_PROFIBUS_Output Structure
|
|
|
|
```
|
|
// Block 1
|
|
"ProductNumber" : Word // Product number to set
|
|
"DigitalInputs" : Word // DI1-DI16 from PLC
|
|
"ReqParamType1" : Byte // Type of requested parameter 1
|
|
"ReqParamIndex1" : Byte // Index of requested parameter 1
|
|
"ReqParamType2" : Byte // Type of requested parameter 2
|
|
"ReqParamIndex2" : Byte // Index of requested parameter 2
|
|
"ReqParamType3" : Byte // Type of requested parameter 3
|
|
"ReqParamIndex3" : Byte // Index of requested parameter 3
|
|
"ReqParamType4" : Byte // Type of requested parameter 4
|
|
"ReqParamIndex4" : Byte // Index of requested parameter 4
|
|
"EnterCommand" : Word // "Enter" command for requested parameters
|
|
"PLCMeasValue1" : Real // Measurement value 1 from PLC
|
|
"PLCMeasValue2" : Real // Measurement value 2 from PLC
|
|
"PLCMeasValue3" : Real // Measurement value 3 from PLC
|
|
"PLCMeasValue4" : Real // Measurement value 4 from PLC
|
|
"ParamTypeIndex1" : Word // Type and index of parameter 1 to transfer
|
|
|
|
// Continue for all parameters through Block 4
|
|
```
|
|
|
|
### 5.2 Hardware Addressing
|
|
|
|
In the device properties, you'll see I/O addresses assigned to the device. Note these addresses as they'll be used for data exchange.
|
|
|
|
For example:
|
|
|
|
- Input address: %IB0 to %IB127 (for 128 bytes of input data)
|
|
- Output address: %QB0 to %QB127 (for 128 bytes of output data)
|
|
|
|
### 5.3 Programming for Data Exchange
|
|
|
|
#### Reading Input Data (OB Cyclic Interrupt)
|
|
|
|
```
|
|
// Create a cyclic interrupt OB (e.g., OB30) that executes every 100ms
|
|
|
|
// Read block 1 (bytes 0-31)
|
|
MOVE %IB0 #DB_PROFIBUS_Input.Status_mPDS
|
|
MOVE %IB1 #DB_PROFIBUS_Input.NotUsed
|
|
MOVE %IW2 #DB_PROFIBUS_Input.ProductionLineStatus
|
|
MOVE %IW4 #DB_PROFIBUS_Input.ProductNumber
|
|
MOVE %IW6 #DB_PROFIBUS_Input.ProductTypeNumber
|
|
MOVE %ID8 #DB_PROFIBUS_Input.RequestedParam1
|
|
MOVE %ID12 #DB_PROFIBUS_Input.RequestedParam2
|
|
MOVE %ID16 #DB_PROFIBUS_Input.RequestedParam3
|
|
MOVE %ID20 #DB_PROFIBUS_Input.RequestedParam4
|
|
MOVE %ID24 #DB_PROFIBUS_Input.MeasValue1
|
|
MOVE %ID28 #DB_PROFIBUS_Input.MeasValue2
|
|
|
|
// Continue for all blocks
|
|
```
|
|
|
|
For SCL programming, you can use a more efficient approach with UDTs and AT constructs:
|
|
|
|
```SCL
|
|
// In OB30 (cyclic interrupt)
|
|
// Map the entire input area to the DB structure
|
|
DB_PROFIBUS_Input.InputData := %IB0;
|
|
```
|
|
|
|
#### Writing Output Data (FC or FB)
|
|
|
|
```
|
|
// Create a function (FC) or function block (FB) for writing data
|
|
|
|
// Set product number
|
|
MOVE #DB_PROFIBUS_Output.ProductNumber %QW0
|
|
|
|
// Set digital inputs
|
|
MOVE #DB_PROFIBUS_Output.DigitalInputs %QW2
|
|
|
|
// Set request parameters
|
|
MOVE #DB_PROFIBUS_Output.ReqParamType1 %QB4
|
|
MOVE #DB_PROFIBUS_Output.ReqParamIndex1 %QB5
|
|
MOVE #DB_PROFIBUS_Output.ReqParamType2 %QB6
|
|
MOVE #DB_PROFIBUS_Output.ReqParamIndex2 %QB7
|
|
MOVE #DB_PROFIBUS_Output.ReqParamType3 %QB8
|
|
MOVE #DB_PROFIBUS_Output.ReqParamIndex3 %QB9
|
|
MOVE #DB_PROFIBUS_Output.ReqParamType4 %QB10
|
|
MOVE #DB_PROFIBUS_Output.ReqParamIndex4 %QB11
|
|
|
|
// Set "Enter" command
|
|
MOVE #DB_PROFIBUS_Output.EnterCommand %QW12
|
|
|
|
// Continue for all blocks
|
|
```
|
|
|
|
For SCL programming:
|
|
|
|
```SCL
|
|
// In a function block
|
|
%QB0 := DB_PROFIBUS_Output.OutputData;
|
|
```
|
|
|
|
## 6. Programming Examples
|
|
|
|
### 6.1 Example: Reading CO2 Measurement
|
|
|
|
```SCL
|
|
// Assuming MeasValue1 contains CO2 concentration in g/L
|
|
// Read the value and check for alarm conditions
|
|
|
|
#CO2_Concentration := "DB_PROFIBUS_Input".MeasValue1;
|
|
|
|
// Check for alarm condition
|
|
IF #CO2_Concentration > #CO2_HighLimit THEN
|
|
#AlarmHighCO2 := TRUE;
|
|
ELSE
|
|
#AlarmHighCO2 := FALSE;
|
|
END_IF;
|
|
|
|
IF #CO2_Concentration < #CO2_LowLimit THEN
|
|
#AlarmLowCO2 := TRUE;
|
|
ELSE
|
|
#AlarmLowCO2 := FALSE;
|
|
END_IF;
|
|
```
|
|
|
|
### 6.2 Example: Changing a Parameter
|
|
|
|
```SCL
|
|
// Change the offset parameter for Original Extract measurement
|
|
// Assuming parameter type 3 = Offset and index 2 = Original Extract
|
|
|
|
// Prepare data
|
|
"DB_PROFIBUS_Output".ParamTypeIndex1.%B0 := 3; // Type: Offset
|
|
"DB_PROFIBUS_Output".ParamTypeIndex1.%B1 := 2; // Index: Original Extract
|
|
"DB_PROFIBUS_Output".ParamValue1 := 0.15; // New offset value: 0.15
|
|
|
|
// Generate Enter command trigger (change the value)
|
|
IF "DB_LastEnterCommand" = 0 THEN
|
|
"DB_PROFIBUS_Output".EnterCommandParams := 1;
|
|
ELSE
|
|
"DB_PROFIBUS_Output".EnterCommandParams := 0;
|
|
END_IF;
|
|
"DB_LastEnterCommand" := "DB_PROFIBUS_Output".EnterCommandParams;
|
|
|
|
// Wait for 2 seconds before next parameter change (using a timer)
|
|
```
|
|
|
|
### 6.3 Example: Setting a Product
|
|
|
|
```SCL
|
|
// Set product number 12
|
|
"DB_PROFIBUS_Output".ProductNumber := 12;
|
|
|
|
// Verify the product was set correctly by checking input data
|
|
IF "DB_PROFIBUS_Input".ProductNumber = 12 THEN
|
|
"ProductSetCorrectly" := TRUE;
|
|
ELSE
|
|
"ProductSetCorrectly" := FALSE;
|
|
END_IF;
|
|
```
|
|
|
|
## 7. Working with PROFIBUS Data Types
|
|
|
|
### 7.1 Data Types Reference
|
|
|
|
|Data Type|Size|Description|
|
|
|---|---|---|
|
|
|Byte|8 bits|Single byte value (0-255)|
|
|
|Word|16 bits|Two-byte value (0-65535, binary coded)|
|
|
|Real|32 bits|Floating point value, MSB,...,LSB format|
|
|
|Bit|1 bit|Single binary value (0 or 1) for digital I/O|
|
|
|
|
### 7.2 Byte Order Considerations
|
|
|
|
The device uses the MSB (Most Significant Byte) first order for multi-byte values. In the S7-1500, all data is stored in little-endian format. This is handled automatically by the PLC for standard data types, but should be considered when working with custom byte manipulations.
|
|
|
|
For 32-bit Real values, the byte order is:
|
|
|
|
- MSB (Most Significant Byte) first in PROFIBUS transmission
|
|
- The S7-1500 automatically handles the conversion when using REAL data types
|
|
|
|
### 7.3 Accessing Individual Bits
|
|
|
|
To access individual bits in the digital inputs/outputs:
|
|
|
|
```SCL
|
|
// Check if digital input 1 is active
|
|
IF "DB_PROFIBUS_Input".ProductionLineStatus.%X0 THEN
|
|
// DI1 is active
|
|
END_IF;
|
|
|
|
// Activate digital output 3
|
|
"DB_PROFIBUS_Output".DigitalInputs.%X2 := TRUE;
|
|
```
|
|
|
|
## 8. Diagnostics and Troubleshooting
|
|
|
|
### 8.1 PROFIBUS Diagnostics
|
|
|
|
1. In TIA Portal, go to the device view
|
|
2. Right-click on the PROFIBUS device and select "Online & Diagnostics"
|
|
3. Check "PROFIBUS Interface" for general communication status
|
|
4. Check "I/O Addresses" for address assignment
|
|
5. Check "Module information" for module status
|
|
|
|
### 8.2 Common Error Codes
|
|
|
|
|Error|Description|Solution|
|
|
|---|---|---|
|
|
|Error #1|Valve error (Gas pressure too high)|Check valves, ensure proper line pressure|
|
|
|Error #2|Concentration out of range|Check measurement conditions|
|
|
|Error #4|Pressure Gas out of range|Check pressure sensor, ensure proper range|
|
|
|Error #8|Temperature out of range|Check temperature sensor|
|
|
|Error #16|Line pressure out of range|Check line pressure sensor|
|
|
|Error #64|Degassing error|Check impeller/oscillator|
|
|
|Error #128|Air in measuring chamber|Ensure proper liquid flow, purge air|
|
|
|
|
### 8.3 Status Monitoring
|
|
|
|
Create a status monitoring view in your HMI application with:
|
|
|
|
- Communication status indicators
|
|
- Error code display and interpretation
|
|
- Parameter request status
|
|
- Parameter change status
|
|
|
|
### 8.4 Testing Communication
|
|
|
|
Use the "Force table" in TIA Portal to:
|
|
|
|
1. Force input values to test PLC reactions
|
|
2. Force output values to test device reactions
|
|
3. Monitor data exchange in real-time
|
|
|
|
## 9. Best Practices
|
|
|
|
1. **Consistent Data Handling**: Ensure you maintain data consistency by not interrupting parameter writes
|
|
2. **Buffer Time**: Wait 2 seconds after sending the "Enter" command before sending new parameters
|
|
3. **Validation**: Always validate data received from the device before using it in calculations
|
|
4. **Error Handling**: Implement proper error handling and status monitoring
|
|
5. **Documentation**: Document the meaning and purpose of each data point in your application
|
|
6. **Periodic Testing**: Periodically test the communication during normal operation
|
|
|
|
## 10. Appendix
|
|
|
|
### 10.1 Parameter Types Reference (Type values used in data exchange)
|
|
|
|
|Type|Description|
|
|
|---|---|
|
|
|3|Offset|
|
|
|4|Adjustment factor|
|
|
|5|Hi limit|
|
|
|6|HiHi limit|
|
|
|7|Lo limit|
|
|
|8|LoLo limit|
|
|
|9|Product parameter|
|
|
|10|Target value|
|
|
|
|
### 10.2 Sample Configuration Data Block
|
|
|
|
```SCL
|
|
// DB_PROFIBUS_Config
|
|
DATA_BLOCK "DB_PROFIBUS_Config"
|
|
{ S7_Optimized_Access := 'TRUE' }
|
|
VERSION : 0.1
|
|
NON_RETAIN
|
|
STRUCT
|
|
DeviceAddress : USInt := 3; // PROFIBUS address of the device
|
|
UpdateRate : Time := T#100MS; // Update rate for data exchange
|
|
WaitTimeAfterEnter : Time := T#2S; // Wait time after Enter command
|
|
MaxProductNumber : UInt := 65535; // Maximum product number
|
|
|
|
// Parameter limits
|
|
MaxParameters : USInt := 16; // Maximum number of parameters
|
|
MaxParamIndex : USInt := 255; // Maximum parameter index
|
|
|
|
// Communication status
|
|
CommStatus : Bool; // TRUE if communication is OK
|
|
LastErrorCode : Word; // Last error code
|
|
ErrorCount : UDInt; // Error counter
|
|
END_STRUCT;
|
|
END_DATA_BLOCK
|
|
```
|
|
|
|
### 10.3 Further Resources
|
|
|
|
- Siemens Industry Online Support (SIOS): [https://support.industry.siemens.com](https://support.industry.siemens.com/)
|
|
- TIA Portal documentation
|
|
- PROFIBUS PA System Description
|
|
- S7-1500 Programming Manual |