// Block Type: FB
// Block Number: 1786
// Original Network Languages: LAD
// Block Comment:
//   TASK1 PID

FUNCTION_BLOCK "PID_RVS318"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1

VAR_STAT
  PID_CIP_Temp_Proport : Real;
  PID_CIP_Temp_Integral : Real;
  PID_CIP_Temp_Derivat : Real;
  PID : "PIDControl";
END_VAR

VAR_TEMP
  SP_Choose : Real;
END_VAR

BEGIN

  // Network 1: Manual Enable (Original Language: LAD)

  "HMI_PID"."RVS318"."ManualControl"."PidEnable" := ("Procedure_Variables"."Blender_Run"."Latch" AND "HMI_PID"."RVS318"."ManualControl"."ManOut" AND "HMI_Variables_Cmd"."Commands_From_HMI"."CMD_BlenderMaintenance") OR ("gP_CIP_Temp_En" AND "gBlenderCIPMode" AND "HMI_Device"."AVS336"."Out" AND "HMI_Digital"."FSS301"."Filtered" AND "CIP_Program_Variables"."CIP_Run"."Latch");

  // Network 2: Setpoint (Original Language: LAD)
  //   Increasing REAL Temperature Set Point

  IF "gBlenderCIPMode" THEN
    "HMI_PID"."RVS318"."Sp" := "CIP_Program_Variables"."General_Data"."SPTemperature" + "Blender_Constants"."gCIP_SP_DeltaT";
  END_IF;

  IF NOT "gBlenderCIPMode" THEN
    "HMI_PID"."RVS318"."Sp" := 0.0;
  END_IF;

  // Network 3: Setpoint (Original Language: LAD)

  IF "Procedure_Variables"."Blender_Run"."Latch" AND "HMI_Variables_Cmd"."Commands_From_HMI"."CMD_BlenderMaintenance" THEN
    "HMI_PID"."RVS318"."Sp" := "HMI_PID"."RVS318"."Pv";
  END_IF;

  // Network 4: PID Control (Original Language: LAD)
  //   Attenzione al Bit REG_INV !!

  "PID"(D_Sel := "AUX TRUE", FF_Enable := "AUX TRUE", I_Sel := "AUX TRUE", LMN_FAC := 1.0, LMN_OFF := 0.0, MAN_ON := "HMI_PID"."RVS318"."ManualControl"."ManOut", PID_Data := "HMI_PID"."RVS318", PID_Enable := "HMI_PID"."RVS318"."I_ITL" OR "HMI_PID"."RVS318"."ManualControl"."PidEnable", P_Sel := "AUX TRUE", REG_INV := "AUX FALSE");

  // Network 5: Integral PID Inizialize (Original Language: LAD)

  IF "HMI_PID"."RVS318"."I_ITL" THEN
    "HMI_PID"."RVS318"."I_ITL" := FALSE;
  END_IF;

  // Network 6: Valve Output (Original Language: LAD)

  SEL_R(G := "HMI_PID"."RVS318"."ManualControl"."PidEnable", IN0 := 0.0, IN1 := "HMI_PID"."RVS318"."Out");

END_FUNCTION_BLOCK