3.6 KiB
3.6 KiB
!Pasted image 20250511151234.png
@startuml "Process Monitoring System"
' Title and styling
title Process Monitoring System with Signal Conversion
skinparam componentStyle rectangle
skinparam backgroundColor white
skinparam defaultTextAlignment center
' Define main packages
package "Syrup Line" {
rectangle "Syrup Pipe" as syrup #ADD8E6
component "Maselli UR29\nRefractometer" as ur29 #FFDD88
component "ADAM Module\n(RS485 to 4-20mA)" as adam1 #ADD8E6
note bottom of adam1: Converts RS485 to 4-20mA
component "Maselli UR62\nRefractometer" as ur62 #FFDD88
component "ADAM Module\n(RS485 to 4-20mA)" as adam2 #ADD8E6
note bottom of adam2: Converts RS485 to 4-20mA
}
package "Water Line" {
rectangle "Water Pipe" as water #ADD8E6
component "Conductivity 401U3\nProbe" as probe #FFDD88
component "2405 Knick\nTransmitter" as knick #B6D7A8
note bottom of knick: Converts conductivity signals to 4-20mA
}
component "PLC\nControl System" as plc #D5A6BD
' Connections
syrup --> ur29 : "Process\nMeasurement"
syrup --> ur62 : "Process\nMeasurement"
water --> probe : "Process\nMeasurement"
ur29 --> adam1 : "RS485"
ur62 --> adam2 : "RS485"
probe --> knick : "Conductivity\nSignal"
adam1 --> plc : "4-20mA"
adam2 --> plc : "4-20mA"
knick --> plc : "4-20mA"
@enduml
The equipment we tested was:
- Syrup / Brix:
- Maselli UR29 - Reflectometer
- ADAM 4021 converters for connecting the PLC
- ur24_gb_hr.pdf
- Maselli UR62 - Reflectometer
- ADAM 4021 converters for connecting the PLC
- ur62_gb_hr.pdf
- Maselli UR29 - Reflectometer
- Water :
- Clritalia: Conductivity - 401U3-B3C0Y0
- K=1 cm (campo di misura 0-50000 uS)
- 401U -gb
- Stratos Eco 2405 Knick converter for transmitting to the PLC
- K=1 cm (campo di misura 0-50000 uS)
- Clritalia: Conductivity - 401U3-B3C0Y0
Comparative Table: UR62 vs UR24 Refractometers by Maselli
Feature | UR62 | UR24 |
---|---|---|
Classification | Basic (THE BASIC) | Advanced (THE ULTIMATE) |
Measurement range | 1.3229 … 1.505 nD (0…85 Bx) | 1.3163 … 1.5318 nD (0…95 Bx) |
Accuracy | • +/- 0.0004 nD (+/-0.2 Bx) alone • +/- 0.0002 nD (+/-0.1 Bx) with RC24 |
• +/- 0.00003 nD (+/-0.02 Bx) SA version • +/- 0.00007 nD (+/-0.05 Bx) HA version • +/- 0.0002 nD (+/-0.15 Bx) STD version |
Repeatability | • +/- 0.2 alone • +/- 0.03 with RC24 |
Not specified |
Product temperature | -25…+90°C (-13…194°F) | • -5…+105°C (23…221°F) • -5…+140°C (23…284°F) for LP version |
Max sterilization temperature | Hot water at 95°C x 30 min Steam (0.5 bar) at 110°C x 30 min |
• 125°C x 30 min • 145°C x 30 min for LP version |
Line pressure | • Max. 10 bar at 20°C • Max. 8 bar at 90°C |
• Max. 10 bar at 20°C • Max. 8 bar at 100°C • Special version up to 40 bar at 20°C |
Power supply | • AC 24V ±10%, 50-60Hz, 80mA • DC 24V ±10%, 80mA |
• AC 24V ±10%, 50-60Hz, 0.6A • DC 24V ±10%, 0.6A • AC 115/230V ±10%, 50-60Hz, 25VA (with transformer) |
Interfaces | Analog, Analog/Digital, PROFIBUS DP, Ethernet/IP | Analog, Analog/Digital, PROFIBUS DP, Ethernet/IP, PROFINET, Modbus/TCP |
Protection | IP67 to EN60529 | IP67 to EN60529 |
Main benefits | • Optical Technology • Basic accuracy • 100% in-line installation • No need of adjustments • No maintenance |
• Optical Technology • High accuracy • 100% in-line installation • No need of adjustments • No maintenance |