If the change is on PLC S7 - 3xx - Reset Totallizer


  • Check that on the BlenderCtrl_MFM Command tha command must be using 1 instead of 3 to reset the counters
IF #mResetWaterTot THEN
    #mWaterVFMCtrl := 1 ;
ELSE
    #mWaterVFMCtrl := 0 ;
END_IF;

IF #mResetSyrupTot THEN
    #mSyrupMFMCtrl :=  1 ;
ELSE
    #mSyrupMFMCtrl := 0 ;
END_IF;

IF #mResetCO2Tot THEN
    #mCO2MFMCtrl := 1 ;
ELSE
    #mCO2MFMCtrl := 0 ;
END_IF;

IF #mResetProductTot THEN
    #mProductMFMCtrl := 1 ;
ELSE
    #mProductMFMCtrl := 0 ;
END_IF;

Resetting Totalizers via PROFIBUS PA (Promass F 300)

1. PROFIBUS Module Mapping

Slot GSD Module Associated Totalizer
9 SETTOT_TOTAL Totalizer 1
10 SETTOT_TOTAL Totalizer 2
11 SETTOT_TOTAL Totalizer 3

Each slot represents a 5byte output block sent from the master to the transmitter.

Byte Layout (Master → Instrument)

Byte Field Purpose Allowed Values
1 SETTOT Control command ==0=Run (totalise)
1=Reset
2=Preset==
2 MODETOT¹ Counting mode 0 = Balance
1 = Only+
2=Only
3= Stop
35 Reserved

¹ The short module (default) omits MODETOT; only the long variant includes it.

Byte Layout (Instrument → Master)

Byte Field Description
14 TOTAL Current totalizer value (IEEE754 float)
5 STAT Quality & status bits (0x80 = GOOD)

2. Resetting a Single Totalizer

  1. Identify the slot of the target totalizer (9, 10 or 11).
  2. Write 1 to Byte1 (SETTOT) of that slot.
  3. Wait one bus cycle (≈10100 ms).
  4. Write 0 back to Byte1 to resume counting.
  5. Read TOTAL (bytes14 in the corresponding input module) and verify it is 0.0.

Example Reset Totalizer 2 Slot 10 / Byte 1 = 1 → 0


3. Resetting All Totalizers

  • Issue the 1 command simultaneously to Byte1 of Slots 9, 10 and 11 or
  • Activate the configurable discrete input “Reset all totalizers” for at least the debounce time (5200ms).