1. Goal

Implement the control logic for a two-format bottle loop consisting of the Accumulation Table, Curve 1, Divider, Combiner, Curve 2 and the format-change axes. Only the loop, table and format-change logic are in scope.


2. Physical Layout

AccumTable → Curve 1 (M344) → Divider → Combiner (M311 + M312) → Curve 2 (M315) → AccumTable


3. Runtime Data held by every entity

Field Type Meaning
formatId INT Active bottle format
cycleMode ENUM {AUTO, MAN} Automatic / Manual
alarmBits DWORD Active alarms bitmap
topAlarm WORD Highest-priority alarm code

4. Main Operating States

  1. Load fill outermost channels first.

  2. Bypass straight-through flow.

  3. Unload empty innermost channels first.


5. Functional Behaviour (concise)

Sub-system Key rules of operation
Accumulation Table • Works in three states (Load, Bypass, Unload).• Channels are filled from the outside in and emptied from the inside out; channels that lie between the selector and the active channel must run while bottles cross them.
• Each channel keeps two virtual counters firstBottle_mm & lastBottle_mm, initialised to the full channel length when a bottle is detected and decremented by the conveyor encoder; when firstBottle_mm == 0 the leading bottle has reached the channels end.
• Once a channel starts Unload it must run until lastBottle_mm == 0 to avoid trapping product.
Curve 1 / Curve 2 • Curve 1 runs in speed-follower mode slaved to the Divider and may move only while the Divider is running.• Curve 2 is slaved to the Combiner and must run whenever the Combiner runs; the two curves are the only places where line accumulation may build up.
Combiner • Speed follows the Divider.• Stops if the downstream photo-sensor pth_out detects more than one bottle; if Combiner stops it also stops the Divider.
Doser Pair • Two motors run in mirror at identical speed; if either trips, both stop.• After the last bottle pulse the pair runs an additional distance (stopDist_mm) using a virtual encoder before stopping.

6. Key Parameters

bottleLen_mm, minAccumTime_ms, loadSpeed_mmps, unloadSpeed_mmps, bypassSpeed_mmps, virtualEncRatio_HzPerMm, safetyGapIn_mm, safetyGapOut_mm


7. Software Architecture (Function Blocks)

FB Name Purpose Typical DB
FB_FormatAxis Position a single minimotor to the target format dimension DB_FormatAxis_<axis>
FB_ChannelSelector Position the infeed/outfeed selector to a channel DB_SelIn, DB_SelOut
FB_AreaTracker Track firstBottle / lastBottle and drive an area motor DB_Area_<n>
FB_DoserPair Run a left/right doser pair with stop-after-pulse logic DB_DoserIO
FB_BufferLogic High-level coordinator for Load / Bypass / Unload DB_Buffer
FB_CombinerCtrl Synchronise Combiner with Divider, stop on blockage DB_Combiner
FB_LoopCurve Slave Curve 1 to Divider and Curve 2 to Combiner DB_Curve1, DB_Curve2

8. Interfaces (concise examples)

FB_FormatAxis

Inputs : enable, dimSet_mm, cycleMode, cmdHoming, jogFwd, jogRev, reset
Outputs: inPosition, positioning, errorWord

FB_ChannelSelector

Inputs : enable, channelSet(0-9), cycleMode, cmdHoming, jogFwd, jogRev, reset
Outputs: inPosition, positioning, autoActive, errorWord

FB_AreaTracker

Inputs : enable, speedRef_mmps, bottleLen_mm, spacing_mm, areaDim_mm
Outputs: areaEmpty, noBottleAtIn, noBottleAtOut

FB_DoserPair

Inputs : enable, speedRef_mmps, bottlePulse, stopDist_mm
Outputs: running, errorWord

FB_BufferLogic

Inputs : reqLoad, reqFormatChange, unloadEnable, bypassSpeedRef
Outputs: tableNeedsProduct, formatChangeOK, outfeedSpeedRef, bypassActive

FB_CombinerCtrl

Inputs : dividerSpeedRef_mmps, pthOutBlocked, dividerRunning
Outputs: combinerSpeedRef_mmps, stopDivider

9. Naming Guidelines

Category Convention Example
FBs FB_<Meaning> FB_BufferLogic
BOOL var verbNounFlag enableMove
WORD camelCase errorWord
REAL suffix _mm, _mmps speedRef_mmps
Structs ST_<Role> ST_AreaStatus

10. Signal Map (I/O)

Signal Suggested Name Dir Comment
i1 ringOutReq IN Product request from downstream
i2 loadCmd IN Start load for format change
i3 ringEmptyOk IN Loop & Divider ready for change
i4 bypassSpeedRef IN Desired bypass speed
i5 formatChangeCmd IN HMI executes change
i6 unloadEnable IN Allow automatic unload
o1 tableProdReq OUT Table ready, asks for bottles
o2 formatChangeOK OUT Loading done & loop empty
o3 outfeedSpeedRef OUT Speed reference to ring outfeed
o4 bypassActive OUT Table in bypass state

11. State Sequence Summary

  1. External loadCmd → BufferLogic enters Load, enforcing outer-to-inner rule.

  2. On HMI formatChangeCmd, BufferLogic finishes load, waits for ringEmptyOk, then raises formatChangeOK.

  3. After format change, BufferLogic triggers Unload (inner-to-outer).

  4. When all channels empty, state switches to Bypass and bypassActive is set.


This version retains the tight structure and English terminology from the previous draft while adding the essential operating descriptions for the Accumulation Table, Curves, Combiner and Doser logic drawn from the original Spanish document.