(* @PATH := '\/Danfoss FC' *)
|
||
TYPE FC_Control_Word
|
||
STRUCT
|
||
B00_RefValue_LSB : BOOL ; (* Choose between the four reference values, which are pre-programmed in par.3-10 *)
|
||
B01_RefValue_MSB : BOOL ;
|
||
B02_Brake : BOOL ; (* Bit 02 = 0 leads to DC braking and stop.
|
||
Bit 02 = 1 leads to ramping. *)
|
||
B03_Coast : BOOL ; (* Bit 03 = 0 causes the frequency converter to immediately "let go" of the motor, so that it coasts to a standstill.
|
||
Bit 03 = 1 enables the frequency converter to start the motor if the other starting conditions have been fulfilled. *)
|
||
B04_QuickStop : BOOL ; (* Bit 04 = 0 causes a stop, in which the motor speed is ramped down to stop via par. 3-81. *)
|
||
B05_HoldOutputFrequency : BOOL ; (* Bit 05 = 0 causes the present output frequency (in Hz) to freeze. *)
|
||
B06_RampStop : BOOL ; (* Bit 06 = 0 causes a stop, in which the motor speed is ramped down to stop via the selected ramp down parameter.
|
||
Bit 06 = 1 permits the frequency converter to start the motor, if the other starting conditions have been fulfilled. *)
|
||
B07_Reset : BOOL ; (* Reset of a trip is activated on the signal’s leading edge, i.e. when changing from logic "0" to logic "1". *)
|
||
B08_Jog : BOOL ; (* Bit 08 = 1 causes the output frequency to be determined by par. 3-19. *)
|
||
B09_RampSelection : BOOL ; (* Bit 09 = 0 means that ramp 1 is active (parameters 3-40 to 3-47).
|
||
Bit 09 = 1 means that ramp 2 (par. 3-50 to 3-57) is active.*)
|
||
B10_DataValid : BOOL ; (* Bit 10 = 0 causes the control word to be ignored,
|
||
Bit 10 = 1 causes the control word to be used. *)
|
||
B11_Relay01Active : BOOL ; (* Bit 11 = 1 Relay 01 activated, provided Control word bit 11 has been chosen in par. 5-40.*)
|
||
B12_Relay04Active : BOOL ; (* Bit 12 = 1 Relay 04 activated, provided Control word bit 12 has been chosen in par. 5-40.*)
|
||
B13_SetUp_LSB : BOOL ; (* Choose between the four menu set-ups, only possible when Multi-Set-ups is selected in par. 0-10. *)
|
||
B14_SetUp_MSB : BOOL ;
|
||
B15_Reverse : BOOL ;
|
||
END_STRUCT
|
||
END_TYPE
|
||
(* @END_DECLARATION := '0' *)
|