Layout:


!Pasted image 20240408155616.png

Added photocells:


!Pasted image 20240408151720.png

The flow now is:


  1. Neumatic Divider M90:
    1. Left: go to M90 - M91 - M92 - M98 - M99
      1. Dosser: M161 (minimotor Guide) - M157/M158 ( sinamics G120 one inverter two motors )
      2. Elevator: M93 - M94/M122
      3. Pneumatic Ejector
      4. M100 - M101
      5. ==Labeler==
      6. M102
      7. Combiner M103 : S1-M103
      8. M107 : infeed Filler
      9. ==Filler==
    2. Right:
      1. M95 - M96 - M97
      2. M104 - M105
      3. Combiner M106 : S1-M106
      4. M107 : infeed Filler
      5. ==Filler==

Synoptic changes:


!Pasted image 20240311170450.png

  • Added Zone 7 and updated Zone 4,5 and 6.

Used Logic "FC TTOP AUTEFA 2 PH"


  • This logic uses 4 fix speed

  • 3 Sensors:

    • NxSA : Next motor SA photocell -> Timer 04 / 05-06 Jam
    • NxSB: Next motor SB photocell -> Timer 06 Jam
    • SA : actual motor SA photocell -> Timer 03 / 05 Jam
    • SA : Timer 01: SA
    • SB : Timer 02: SB
  • FIX1: ( empty )

    • By default
  • FIX2: only 1 photocell accumulation

    • NxSA e non SA e SB
  • FIX3: 2 photocells accumulation

    • No SA + SB + NxSA o SA + SB NO NxSA : Two photocells but not 3
  • FIX4: 3 photocells ( Full )

    • All 3 photocells

Doser M157/M158 with thermal sensor


  • Added sensor signals on E47.5 / E47.6
  • Added Allarm "DB Warnings".W173_01_7

Added Minimotor logic for Guide changer


  • Added Minimotor Logic FC1155 for the M161 on the PLC
    • Called from FC380
  • Added 595 page on both HMI to setup the formats and allow manuals.

!Pasted image 20240311121916.png

  • Diametro Bottiglia and Tolleranza Diametro are ==saved on the Recipe== as an array.
  • Add popup for homing

!Pasted image 20240403112756.png

  • On this popup the user must put the length that is currently between the rubber conveyors.

!Pasted image 20240403113511.png

Added Motors to FC371:

      L     %DB319.DBB291        // Motor M98
      T     %DB371.DBB49

      L     %DB320.DBB291        // Motor M99
      T     %DB371.DBB50

      L     %DB321.DBB291        // Motor M100
      T     %DB371.DBB51

      L     %DB322.DBB291        // Motor M101
      T     %DB371.DBB52

      L     %DB323.DBB291        // Motor M102
      T     %DB371.DBB53

      L     %DB324.DBB291        // Motor M103
      T     %DB371.DBB54

      L     %DB325.DBB291        // Motor M157/158
      T     %DB371.DBB55

Added logic for Q1 on FC372


!Pasted image 20240312154910.png

Added signals from and to Henkel


TO HENKEL:

!Pasted image 20240313122842.png DB34: !Pasted image 20240313122638.png

FROM HENKEL:

!Pasted image 20240313122858.png DB33: !Pasted image 20240313122722.png!Pasted image 20240313122746.png

Added new Group of EMD for the Q5 line


  • DB224

!Pasted image 20240321151155.png

Flow selection Check:


!Pasted image 20240408123359.png

This page helps the operator to ensure all flows are ok.

Added Alarms:
  • 173/02/0 General - GUIDE M103 NOT OK FOR THE FLOW SELECTED
  • 173/02/1 General - DIVIDER M90 NOT OK FOR THE FLOW SELECTED
  • 173/02/2 General - DIVIDER LINE FLOW NOT OK FOR THE FLOW SELECTED
  • 173/02/3 General - HENKEL SUPERVISION FLOW NOT CORRECT

Selectors Page:


!Pasted image 20240408123502.png

Pause lowerator infeed:
  • With this selector the lowerator can be emptied to prevent damaging the bottles
Added Alarm:
  • "DB Warnings".W173_06_1 : 173/06/1 General - Stop bottle flow on lowerator
Flow:
  • On this page can be selected the Flow requested. Based on this selection the selected flow motor will be enabled and the other will be disabled.

PE Labeler Counting


  • Added 3 photocells:
  • Reset signal from Henkel from Q1
    • "FromQ1_D".FromHenkel.SignalExchange.Labeller.di14[2]
    • This signal must be connected with "FromQ1_D".FromHenkel.STW."di0.x"[1] from Q3
    • On Q1 with "ToQ3_D".FromHenkel.STW."di0.x"[1]
    • On FC9 segm 10
On Q4:

Q4->Q1 Q1->Q4
Count "ToQ1_D".ToHenkel.Counter.DischargeLabeller
Reset "FromQ1_D".FromHenkel.SignalExchange.Labeller.di14[2]
On Q1 PLC:

FC32 - Net 10:

// Labeller counter Reset
"ToQ4_D".FromHenkel.SignalExchange.Labeller.di14[2] := "ToQ3_D".FromHenkel.STW."di0.x"[1];
    

FC32 - N8:


"ToQ4_D".FromHenkel := "ComHenkel_D".FromHenkel_L23;

"ComHenkel_D".ToHenkel.SignalExchange.Labeller."AlplaGate_L23/L24" :=
"FromQ4_D".ToHenkel.SignalExchange.Labeller."AlplaGate_L23/L24";

"ComHenkel_D".ToHenkel.SignalExchange.Filler :=
"FromQ4_D".ToHenkel.SignalExchange.Filler;

"ComHenkel_D".ToHenkel.SignalExchange.Labeller."di10.x"[8] := "FromQ4_D".ToHenkel.SignalExchange.Labeller."di10.x"[8];
"ComHenkel_D".ToHenkel.SignalExchange.Labeller."di10.x"[9] := "FromQ4_D".ToHenkel.SignalExchange.Labeller."di10.x"[9];

"ComHenkel_D".ToHenkel.SignalExchange.Labeller.di13 := "FromQ4_D".ToHenkel.SignalExchange.Labeller.SpeedReference;

FC9: - N10:

"ToQ3_D".FromHenkel := "ComHenkel_D".FromHenkel_L23;

"ComHenkel_D".ToHenkel.SignalExchange.Labeller."di10.x"[0] := "FromQ3_D".ToHenkel.SignalExchange.Labeller."di10.x"[0];
"ComHenkel_D".ToHenkel.SignalExchange.Labeller."di10.x"[1] := "FromQ3_D".ToHenkel.SignalExchange.Labeller."di10.x"[1];

"ComHenkel_D".ToHenkel.SignalExchange.Labeller.SpeedReference := "FromQ3_D".ToHenkel.SignalExchange.Labeller.SpeedReference;

FC26 - Net 7: This counters depends on which Labeler is in production:

"ToQ4_D".FromHenkel.SignalExchange.Labeller."di10.x"[3] = 0 => MCC in production
"ToQ4_D".FromHenkel.SignalExchange.Labeller."di10.x"[10] = 0 => PE in production

!Pasted image 20240408151045.png

FC6 - Net 3 :

!Pasted image 20240403145852.png

The Q4/Q5 now will only work with L24 signals:


Depends how Henkel will manage this change.

FC32: !Pasted image 20240408144625.png

In the future this will be only L24 so may be HENKEL decide to transfer all info on the L24 Prosoft. So we need to change to:

"ToQ4_D".FromHenkel := "ComHenkel_D".FromHenkel_L24;